Applications:
For the electronic measurement of voltages: AC, DC IMPL.,etc.,with galvanic isolation between the
primary (high voltage) and the secondary (electronic) circuits.
Main technical data:
1. Primary normal voltage VPN: 200V r.m.s
2. Primary voltage, measuring range IP: 0~+/-300V
3. Secondary nominal output: 80mA rms
4. Supply voltage(+/-10%): +/-15V~+/-24V
5. Current consumption: 35mA(@+/-24V)+ Secondary output current
6. Isolation test: Between the primary circuit and the secondary circuit(+.-.M.E): 6kVrms/50Hz/1min
Between the secondary circuit(+.-.M) and the ground-screen(E): 1kVrms/50Hz/1min
Accuracy – Dynamic performance data:
1. Accuracy @ VPN, TA=+25 C: +/-1%
2. Non-linearity @ VPN, TA=+25 C: better than +/-0.1%
3. Offset current≤±0.5mA(@+25℃)
4. Thermal drift: +/-0.5mA(0 C ~+70 C)
5. Response time @90% of VPmax: not more than 30us
General data:
1. Operating temperature: 0oC~+70oC
2. Storage temperature: -40 C ~+85 C
3. Turns ratio: 5000:2500
4. Primary resistance @ TA=+25 C: 5000 ohm
5. Secondary coil resistance: not more than 40 ohm
6. Weight: 2kg
7. Standards: EN 50178
Features:
1. Hall effect measuring principle
2. Galvanic isolation between primary and secondary circuit
3. Insulated plastic case made of black PPO recognized according to UL 94-V0
Dimension:
Connection: