Applications:
For the electronic measurement of currents: AC, DC IMPL.,etc.,with galvanic isolation between the
primary (high power) and the secondary (electronic) circuits.
Main technical data:
1. Primary normal current IPN: 3000A r.m.s
2. Primary current, measuring range IP: 0~+/-5000A
3. Measuring resistance: RMmin RMmax
with +/-15V @ +/-3000A max: 0 ohm 8 ohm
@ +/-3500A max: 0 ohm 2 ohm
with +/-24V @ +/-3000A max: 0 ohm 35 ohm
@ +/-5000A max: 0 ohm 7 ohm
4. Secondary normal current: 300mA rms
5. Conversion ratio: 1:10000
6. Supply voltage(+/-10%): +/-15V~+/-24V
7. Current consumption: 60mA(@±24V)+ Secondary output current
8. Isolation test: Between the primary circuit and the secondary circuit(+.-.M.E): 12kVrms/50Hz/1min
Between the secondary circuit(+.-.M) and the ground-screen(E): 1kVrms/50Hz/1min
Accuracy – Dynamic performance data:
1. Accuracy @ IPN, @+/-15V~+/-24V, @+25 C: +/-0.2%
2. Non-linearity: better than +/-0.1%
3. Offset current: not more than +/-0.4mA(@+25 C)
4. Thermal drift: +/-0.6mA(-25 C ~+70 C)
5. Response time @90% of IP max: not more than 1us
6. dI/dt accurately followed: better than 50A/us
7. Frequency Bandwidth (-1dB): DC 0~100kHz
General data:
1. Operating temperature: -25oC~+70oC
2. Storage temperature: -40 C ~+85 C
3. Secondary coil resistance: not more than 35 ohm
4. Weight: 15kg±2 kg
5. Standards: EN 50155
Features:
1. Hall effect measuring principle
2. Galvanic isolation between primary and secondary circuit
3. Insulated plastic case made of black PPO recognized according to UL 94-V0
Dimension:
Connection: