Min. Order: | 500 Piece/Pieces |
---|---|
Payment Terms: | T/T |
Supply Ability: | 10000 Unit/Units per Month |
Place of Origin: | Zhejiang |
Location: | Ningbo, Zhejiang, China (Mainland) |
---|---|
Business Type: | Manufacturer, Trading Company, Agent, Distributor/Wholesaler |
Model No.: | NT400-S(T) |
---|---|
Means of Transport: | Ocean |
Theory: | Current Sensor |
Usage: | Magnetic Sensor |
Brand Name: | CSR |
Output: | Current |
Primary nominal: | 400Arms |
Production Capacity: | 10000 Unit/Units per Month |
Packing: | up to customer |
Delivery Date: | 4 weeks upon receipt of confirmed order |
400A Excavator transducer Applications:
For the electronic measurement of currents: AC, DC IMPL.,etc.,with galvanic isolation between the primary (high power) and the secondary (electronic) circuits.
Main technical data:
1. Primary normal current IPN: 400A r.m.s
2. Primary current, measuring range IP: 0~±800A
3. Secondary normal current: 200mA rms
4. Conversion ratio: 1:2000
5. Supply voltage(1±10%): ±12V~±18V
6. Current consumption: ≤25mA(+ Secondary output current
7. Isolation test: Between the primary circuit to the secondary circuit(+.-.M): 6kVrms/50Hz/1min
Accuracy – Dynamic performance data:
1. Accuracy @ IPN, TA=+25 oC, ±1%
2. Non-linearity: better than 0.1%, TA=+25 oC
3. Offset current @ IP=0, TA=+25 oC: not more than ±0.25mA
4. Thermal drift: ±0.4mA(-25 oC ~+<a FCK__AnchorC FCK__AnchorC" fck__anchorc="" name="OLE_LINK12">70 oC)
5. Reaction time @10% of IP max : less than 500ns
6. Response time @90% of IPN: not more than 1us
General data:
1. Operating temperature: -25℃~+70℃
2. Storage temperature: -40℃~+85℃
3. Secondary coil resistance: not more than 30ohm
4. Weight: ≤250g
5. Standards: EN 50155
Features:
1. Hall effect measuring principle
2. Galvanic isolation between primary and secondary circuit
3. Insulated plastic case made of black PC recognized according to UL 94-V0
4. The whole current transducer comply with RoHS Directive completely
400A Excavator transducer
Dimension:
Connection: