According to the special requirements of the user's use site, XCA400-500k intelligent AC load bank and its accessories are provided with technical standards in terms of function, performance, use method, structure, installation and test, etc. The need for the unit to carry out a load test.
The system consists of two parts: measurement and control and load, mainly including dry AC load bank, data acquisition system, automatic loading and unloading control system, cooling device, auxiliary control and PC software.
This system combines the dry load module with the automatic measurement and control module, which can detect the output power and load capacity of various generator sets. The system can be used in conjunction with a computer to realize intelligent control, automatically complete the test of the generator set according to the preset power and time, generate tables and graphs, and support printing, free from tedious manual operations, and provide scientific and technical support for high-power generator sets. testing method.
Genset Test System XCA400-500K Parameters
Rated voltage/frequency AC three-phase four-wire 400V/50Hz
Maximum load power Resistive load: 510kW
Load classification Resistive load: 11 grades, 1, 2, 2, 5, 10, 20, 20, 50, 100, 100, 200kW
Power factor 1
Load accuracy (per gear) ±5%
Load accuracy (whole machine) ±3%
Display accuracy 0.5 class
Control power supply External AC three-phase four-wire 380V/50Hz
Wiring method Load power input - copper bar (star connection)
Control power input - aviation plug
Communication interface RS485, RS232
Insulation class F class
Working way Continuous work
Cooling method Forced air cooling, side inlet air, upper air outlet
Transport Lifting, there are load-bearing rings on the top of the chassis and casters on the bottom
Chassis color gray (RAL7035)
Chassis size about 1540 mm×1250mm×1680mm (length×width×height)
Weight about 800kg
Working environment parameters
Working temperature -10℃~+50℃
Relative humidity ≤95%
Altitude ≤2500m
Atmospheric pressure 86~106kPa
Main component brands
Contactor Chint
Fuses Ming Rong
PLC Siemens