user login

NACF.500S5/SP3V Series Current Transducer

Min. Order: 500 Piece/Pieces
Payment Terms: T/T
Supply Ability: 10000 Unit/Units per Month
Place of Origin: Zhejiang

Company Profile

Location: Ningbo, Zhejiang, China (Mainland)
Business Type: Manufacturer, Trading Company, Agent, Distributor/Wholesaler

Product Detail

Model No.: NCA1C-500A/SP5
Means of Transport: Ocean
Theory: Current Sensor
Usage: Magnetic Sensor
Brand Name: CSR
Output: Current
Primary nominal: 500Arms
Production Capacity: 10000 Unit/Units per Month
Packing: up to customer
Delivery Date: 4 weeks upon receipt of confirmed order
Show

Product Description

Applications:
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation betwe
the primary circuit (high power) and the secondary circuit (electronic circuit).

Main technical data:
1. Primary normal current IPN (r.m.s)    Primary current measuring range IP                 Type
                                   500A                                                 +/-900A                                   NCA1C-500A/SP5
2. Supply voltage(+/-5%): +5V
3. Current consumption: 10mA+ Secondary output voltage /loading resistance
4. Isolation test: Between the primary circuit to the secondary circuit(+.-.M): 3kVrms/50Hz/1min
5.   Normal output voltage @RL=10,000 ohm , TA=+25 C: 2.5VĀ±0.5Ip/InpV
6. Loading resistance: more than 1000 ohm

Accuracy ā€“ Dynamic performance Data
1. Accuracy @ IPN, TA=+25 C: +/-2%
2.   Non-linearity (0~ IPN): +/-1% (+25ā„ƒ)(without offset)
3. Electrical offset voltage VOE, TA=+25 C : not more than 2.5V+/-10mV
4. Hysteresis offset voltage @ IP=0,
after an drift of 1x IPN: not more than +/-10mV
5. Thermal drift of VOE: not more than +/-1mV/oC(-10oC~+80oC)
6.   Response time (@ 90% of IP): not more than 5us         
7. di/dt accurately followed:   better than 50A/us
8. Frequency bandwidth(-3dB): DC 0 .. 50kHz

General data:
1. Operating temperature: -10 C ~+80 C
2. Storage temperature: -40 C ~+80 C
3.   Weight: approx. 60g
4. Standards: EN50178

Features:
1. Hall effect measuring principle
2. Galvanic isolation between primary and secondary circuit
3. Insulated plastic case made of white PPO recognized according to UL 94-V0
4. The whole current transducer comply with RoHS Directive completely

Dimension:
NCA1C/SP5 Series Current Transducer
Connection:
NCA1C/SP5 Series Current Transducer
Output Voltage ā€“ Primary Current:
NCA1C/SP5 Series Current Transducer

Post Buying Request