1.1General introduction
APGS different frequency automatic dielectric loss tester is a high-precision instrument, which can be applied to automatically measure electrical loss tangent ( ) and capacitance of all kinds of high voltage electrical equipments' on the spot of power plants, substations etc.
1.2 Technical Index
1. Condition of Use -5℃~40℃, RH<80%
2. Power Source AC 110V±10% Without Frequency Limit
3. High Voltage Output
Range 1KV~10KV, every 1KV
Precision 5%
Maximum Current 140mA
Capacity 1000VA
4. Self-Excited Power
Voltage Range AC 0V~30V;
Frequency 45Hz /55Hz
Maximum Current 15A
5. Definition tgδ: 0.001% ; Cx: 0.1PF
6. Measuring Range tgδ Without Limit
10kV
1kV
CVT Test
7. Size 470mm(L) ×320mm(W)×390mm(H)
8. Weight 30kg