user login

Automatic 10KV Power Transformer Dielectric Loss Tester

Min. Order: 1 Set/Sets
Trade Term: FOB
Payment Terms: Paypal, L/C, T/T
Supply Ability: 1000/month
Place of Origin: Chongqing

Company Profile

Location: Chongqing, China (Mainland)
Business Type: Manufacturer, Trading Company
Main Products: Oil Purifier, Oil Tester

Product Detail

Model No.: GDGS
Means of Transport: Ocean, Air, Land
Power: Electronic
Brand Name: gold
Application: Six Phase Protection Relay Test Set
Production Capacity: 1000/month
Packing: Veneer case
Delivery Date: 15 days after payment
Show

Product Description

Introduction:

  • GDGS Automatic 10KV Power Transformer Dielectric Loss Tester  is used to measure dissipation factor (PF) in heavy interference site such as power plants or power substations.

  • It can also be used in laboratory for high accurate test. The set is whole in one designed: including precision digital bridge, power unit, reference capacitor (CN), step-up transformer and other electronic circuits. 

  • It's also using frequency shift technology, FFT (Fast Fourier Transform algorithm) and digital filtering. When started, it's running automatically and then outputs the results on LCD display and prints the results automatically.

  •  

    Specifications:

    No.ItemGDGS Automatic 10KV Power Transformer Dielectric Loss Tester
    1Accuracy

    Cx±(reading×1%+1pF)

    PF±(reading×1%+0.00040)

    2Interference RatioInterference current is no more than 2 times of test current
    3Capacitance RangeInternal HV:  3pF~60000pF / 10kV,60pF~1uF/0.5kV
    External HV  3pF~0.3uF/10kV
    Resolution  0.0001pF, 4 digital
    4PF RangeNo limit, Resolution 0.001%, C/L/R specimen test
    5Input current range10μA~1A
    6Internal HV0.5~10kV / 200mA (max)
    7HV AdjustRise or fall smoothly
    8HV Accuracy±(reading×1%+10V) Resolving 1V
    9Frequency select60Hz single point, locked 55Hz/65Hz double point, locked
    10Test Time40S typical
    11Power Supply180V~270V 50Hz/60Hz auto
    12Operating Temperature0℃~60℃
    13Storage Temperature-20℃~60℃
    14Humidity<90%

     

     

    Package List:

  • The GDGS Automatic 10KV Power Transformer Dielectric Loss Tester;         

  • User's manual and quality certification;

  • Test cable;

  •  Main lead;

  •  Additional color ribbon, paper roll and fuse;


Post Buying Request