1.DTS1032 three phase electronic energy meter uses the large-scale appropriative integrated circuit,according to the international advanced technology,the design is unique and the work-manship is exquisite.
2.In the various segments of design,production,testing,factory inspection,aging,etc,we put the high reliability as our main objective.Compared with the induction meter,this meter is of high measuring accuracy,good stability,small volume,light weight,low power consumption and it is easy to realize and expand the modern management function.It also has the indicator of loss of phase.
3.It adopts to output the electric energy pulse signal with photoelectricity isolation technique and remote pulse output interface with extensibility,meanwhile it can use for power carrier.It is suitable for 50Hz three phase active energy meter.
4.The meter can install fixedly inside or outside the electric instrument box for use.]
Standards:
GB/T15283-94,GB/T17215-2002,GB/T17215.321-2008 and other correlative Chinese standards;
IEC521-1998,IEC61036:2000,IEC62053-21:2003 and other correlative international standards.
Technical parameters
Type | Accuracy Class | Rated Voltage(V) | Rated Current (A) |
DTS1032 | 1.0/2.0 | 3*220/380 3*57.7/100 | 3*1.5(6),3*3(6),3*5(20),3*10(40),3*15(60),3*20(80),3*30(100) |
DSS1032 | 1.0/2.0 | 3*100 3*380 | 3*1.5(6),3*3(6),3*5(20),3*10(40),3*15(60),3*20(80),3*30(100) |
DXS1032-T | 2.0 | 3*220/380 3*57.5/100 | 3*1.5(6),3*3(6),3*5(20),3*10(40),3*15(60),3*20(80),3*30(100) |
DXS1032-S | 2.0 | 3*100 3*380 | 3*1.5(6),3*3(6),3*5(20),3*10(40),3*15(60),3*20(80),3*30(100) |
1)Phase: three phase
2)Display type: analog display and digital display
3)Reference frequency: 50Hz
4)Meter constant: 200imp/KWH~1600imp/KWH(according with the cover marking)
5)Start
Under the condition of rated current,the meter should start and continuously record.
Meter | The meter accuracy class | The power factor |
1 | 2 | 3 |
Direct type | 0.004Ib | 0.05Ib | 0.01Ib | 1.0 |
Through the voltage and current transformer type | 0.002Ib | 0.003Ib | 0.005Ib | 1.0 |
6)Potential action
When put on 115% rated voltage,and the current return has no current,the electricity output is less than one pulse.
7)Technical specs
Normal working voltage: 0.9-1.1Un rated voltage;
Limit working voltage: 0.8-11.5Un rated voltage
8)Power consumption: ≤2W 10VA
9)Temperature condition
Normal working temperature:-10℃~45℃
Limit working temperature: -50℃~65℃
Storage & transporation temperature: -25℃~70℃
10) Relative humidity: ≤75%
11) Weight: about 1.2kg
12) Dimension:230mm×142mm×73mm