user login

Infrared Flame Detector

Min. Order: 10 Piece/Pieces
Supply Ability: 100,000pcs/month
Place of Origin: Zhejiang

Company Profile

Location: Ningbo, Zhejiang, China (Mainland)
Business Type: Manufacturer, Trading Company

Product Detail

Model No.: 3B-BK51/IR3/CCTV
Usage: Others
Production Capacity: 100,000pcs/month
Delivery Date: 15 days
Show

Product Description

Basic Technical Parameters
1.Monitoring Angle:≤90°
2.Ambient Temperature:-40~70degree centigrade
3.Fire response time:<10S
4.Ambient Humidity:≤95RH(40 + 270degree centigrade)
5.Spectral Response:0.7~1.0umIR,4.0~4.4umIR,5~6umIR
6.Detection Distance:30m(0.1square meter  petrol fire)
7.CCTC image: closed-circuit real-time image of the 0.1square meter petrol fire alarm monitoring zone 30m away
Electrical Parameters
1.Operating Voltage:18V~32VDC
2.Indicator Lamp: flash for normality and keep lighting for alarm
3.Operating Current:≤20mA in a standby status (24VDC)≤40mA (24VDC)in an alarm status
4.Output Mode:relay output--------for normality:the contacts of the fault relay are normally closed,while the contacts of the fire alarm relay are normally open
for fault:
the contacts of the fault relay become normally open from the normally closed status
for alarm:
the contacts of the fire alarm relay become normally closed from the normally open status
Rating of contact:0.5A
/125VAC 1A /30VDC 0.3A/ 60VDC
4-20mA Output-------For Fault:0+0.5mA For Normality:
5 mA±10%
For Early Warning:12mA±10% For Fire Alarm:
18mA±10%
RS-485 Output------- RS-485 standard interface for being connected with equipment such as controllers
5.Color video: Standard CATV interface, NTSC or PAL transformation, which are suitable for monitoring, recording and scanning carried out by various standard image apparatuses
Post Buying Request