- Monitoring Angle:≤90°
- Fire Response Time:<10S
- Spectral Response:0.7~1.0umIR,4.0~4.4umIR,5~6umIR
- Ambient Temperature:-40~70 Degree Centigrade
- Ambient Humidity:≤95RH(40 + 2Degree Centigrade)
- Detection Distance:45m(0.1 square meter petrol fire)
Electrical Parameters
1.Operating Voltage:18V~32VDC
2.Indicator Lamp: flash for normality and keep lighting for alarm
3.Operating Current:≤20mA in a standby status (24VDC)≤40mA (24VDC)in an alarm status
4. Output Mode:relay output--------for normality:the contacts of the fault relay are normally closed,while the contacts of the fire alarm relay are normally open
for fault:the contacts of the fault relay become normally open from the normally closed status
for alarm:the contacts of the fire alarm relay become normally closed from the normally open status
Rating of contact:0.5A /125VAC 1A /30VDC 0.3A/ 60VDC
4-20mA Output-------For Fault:0+0.5mA For Normality:5 mA±10% For Fire Alarm:18mA±10%
RS-485 Output-------RS-485 standard interface for being connected with equipment such as controllers