Min. Order: | 1 Piece/Pieces |
---|---|
Payment Terms: | T/T |
Place of Origin: | Shanghai |
Location: | Shanghai, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Analog Data Acquisition Modules, Ethernet 16channels 0-3V 0-4V 4-20mA Modbus-TCPIP Converter, Modbus RTU, Ethernet 16 Channels Normal Open Relay Output Modbus Tcpip, Analog Input Modules |
Model No.: | S5134 |
---|---|
Brand Name: | SHJ |
S5134 is a high quality and low cost analog data acquisition module with 8 universal analog inputs. Each input can be 0-5V,0-10V,0-20mA,thermistor,dry contact, open-collector input,8 channels 0-10V analog output,3 isolated digital input and 8 channels isolated open-collector digital output. The digital input can be dry contact, wet contact and open-collector, each input also can be 32-bit counter.S5134 has RS485 and rj45 two type interface,rs485 support standard Modbus RTU protocol and RJ45 support Modbus Tcpip protocol.It can easy integrate with PLC and labview with standard Modbus/Modbus Tcpip protocol
Highlights
Surge-protected analog inputs with 12-bit resolution and 100k sample speed
Input can be any combination of 0-5V,4-20mA,0-10V,NTC 10K thermistor, open-collector and dry contact
The channel number is configurable, can be set up from 1 channel through 8 channels, for analog input and set up from 1 to 6 for digital input, improve sample rate for small count input
8 channels 0-10V analog output with high accurate reference chip
Isolated digital inputs can be configured as counter input, total 32 bits,1000Hz
Total 8 channels isolated open-collector digital output
Standard ModBus TCPIP protocol,easy work with PLC
Standard ModBus protocol allows for up to 254 unique devices on one RS485 network
A lot of spare FLASH can be used to store user's parameters
Can update your firmware via ISP through RS485 network, can provide any hex file to help you finish some logic control
DIN support available
Application:
Remote data acquisition
Process monitoring
Industrial process control
Energy management
Supervisory control
Security systems
Laboratory automation
Building automation
Product testing
Direct digital control
Technical data:
Analog Input Resolution--------------------------------------------------------------------------------12-bit
Analog Input Channel Number------------------------------------------------------------------------------8
Analog Input range----------------------0-5V,0-10v,0-20mA, thermistor, dry contact,open-collector
Analog Input Protection---------------------------------------------------------------------Lightning,static
Analog Input Accuracy---------------------------------------------------------------------------------±0.1%
Analog Input Zero drift-----------------------------------------------------------------------------±3uV/C
Analog Input Sample Rate-----------60 sample/second(8 channels),900 sample/second(1 channel)
Analog Output Resolution-----------------------------------------------------------------------------12-bit
Analog Output Channel Number--------------------------------------------------------------------------8
Analog Output Range----------------------------------------------------------------------------------0-10V
Analog Output Accuracy--------------------------------------------------------------------±0.2% of FSR
Analog Output Zero Drift------------------------------------------------------------------------±30uV/C
Digital Input Channel Number----------------------------------------------------------------------------- 3
Digital Input Range-------------------------------------------------------------------------------+4V~+36V
Digital Input Signal----------------------------------------------wet contact, dry contact, open-collector
Digital Input Counter Frequency-------------------------------100Hz@6channels;1000Hz@1channel
Digital Input Counter Length---------------------------------------------------------------------------32-bit
Output channel number------------------------------------------------------------------------8
Output signal---------------------------------------------------------------------open-collector
Output current----------------------------------------------------------------maximum 40mA
Output BUS----------------------------------------------------------------------------------Ethernet/RS485
RS232/RS485 protocol--------------------------------------------------------------MODBUS/RTU
Ethernet protocol------------------------------------------------------------------MODBUS/TCPIP
Output Protection-----------------------------------------------------------------------------Lightning,static
Power input----------------------------------------------------------------------------------15~24V(AC/DC
Power consumption------------------------------------------------------------------------------------<0.6W
Ambient temperature:
Operation-------------------------------------------------------------------------- -20~85C(-4~185F)
Storage---------------------------------------------------------------------------------------- -40~125C(-40~257F)
Ambient humidity-----------------------------------------------------------------------------------------------10%~90%RH
Material,enclosure-----------------------------------------------------------------------Flame proof plastic
Enclosure rating--------------------------------------------------------------------------------------------IP31
Colour----------------------------------------------------------------------------------------------White/Black
Size---------------------------------------------------------------------------------------------115*90*43 mm
Wiring diagram and description:
Top view figure
Communication wiring diagram
Analog inputs wiring diagram
Analog outputs wiring diagram
Dry contact wiring diagram
Dry contact wiring diagram
Isoalted digital output wiring diagram
Inputs
Each analog input can be jumper-configured in 1 of 4 ways:
0-5V signal
0-10V
0-20mA
Dry contact, thermistor, open-collector. thermistor default is 10K NTC, but can custom according to your sensor type
All digital inputs can be jumper-configured in 1 of 2 ways:
Wet contact input
Dry contact, open-collector input
PINs and LEDs
Power supply
24VAC: power supply positive input, has reverse protection, accept AC and DC input
- : Power supply negative input
RS485 Port
B: Connect to B of RS485
A: Connect to A of RS485
R: Connect to GND for RS485
Ethernet port
Connect to local Ethernet network through RJ45 cable
Inputs
Analog:
A1 ~ A8: Analog input 1 through 8
AGND: common for analog input 1 through 8,also use for analog output
Digital:
DVCC: Power source input for digital input 1 through 3,wet contact input available
D1 ~ D3: Digital input channel 1 through 3
DGND: common for digital input 1 through 6, available in dry input mode
Outputs
Analog:
AO1 ~ AO8: Analog output 1 through 8
AGND: common for analog output 1 through 8,also use for analog input
Digital:
O1~O8: Digital output channel 1 through 8
OGND: common GND for digital output 1 through 8
Leds
BEAT: Will flash when system is working
Comm: Will flash when RS485 serial port communication