XIANCE XCA10.5-2000K medium voltage generator set intelligent test system
It adopts fin-type power consumption resistance, Siemens PLC control and comprehensive alarm system, which can effectively carry out load test on 10kv medium voltage. Its characteristics are that it is practical, convenient and flexible, low thermal power density, and safety-oriented.
Parameters of XCA10-2000K medium voltage generator set intelligent test system
Rated voltage/frequency AC three-phase four-wire 10500V/50Hz
Maximum load power Resistive load: 2000kW
Load classification Resistive load: divided into 5 grades, 200, 450, 450, 450, 450kW
Power factor 1
Load accuracy (per gear) ±5%
Load accuracy (whole machine) ±3%
Display accuracy 0.5 class
Control power supply External AC three-phase four-wire 380V/50Hz
Wiring method Load power input - copper bar (star connection)
Control Power Input - Terminal Block
Communication interface RS485, RS232
Insulation class F class
Maximum protection class IP54
Working way Continuous work
Cooling method Forced air cooling, side inlet air, upper air outlet
Chassis Construction Containerized with ladder access to the top, air inlet and outlet with grille and protective door
Transport Lifting, there are load-bearing rings on the top of the chassis
Chassis color gray (RAL7035)
Chassis size about 6058mm × 2350 mm × 2591mm (length × width × height)
Weight about 6000kg
Working environment parameters
Working temperature -10℃~+50℃
Relative humidity ≤95%
Altitude ≤2500m
Atmospheric pressure 86~106kPa
Covers an area of about 14.77 square meters
The ground load-bearing requirement is about 406 kg/square meter on average
Ventilation distance The air inlet is required to be 3 to 5 meters free of obstacles
The air outlet is more than 3 meters away from the roof or other obstacles
Reserved distance To facilitate entry, there should be no obstacles 3 meters in front of the control room
There should be no obstacles 2 meters in front of the maintenance room
Safe working distance There should be an isolation fence 1 meter away from the load cabinet
When the load cabinet is working, there should be no staff within 3-5 meters
Test cable requirements The current through each phase of the test cable between the generator set and the load cabinet is about 110A
Main component brands
Contactor Sunlight
Fuse Chuantai
PLC Siemens