Min. Order: | 1 Set/Sets |
---|---|
Trade Term: | FOB, |
Payment Terms: | T/T |
Supply Ability: | 10 |
Place of Origin: | Hubei |
Location: | Wuhan, Hubei, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Model No.: | TKBPXZ |
---|---|
Frequency regulation sensitivity: | 0.1Hz |
Working time: | Full power continuous working time of 60min |
Resonance voltage waveform: | Pure sine wave waveform distortion rate≤1.0% |
Production Capacity: | 10 |
Product Description
Transformer GIS SF6 switch CT/PT insulator bus bar cable bushing and others capacitive devices are the common primary electric equipments.
The complete set of frequency conversion series resonance test equipment is mainly used for ac withstand voltage test of cross-linked cable, hydraulic generator, main transformer, bus GIS etc.
The complete set of frequency conversion series resonance test equipment is mainly composed of frequency conversion control power, supply excitation ,transformer reactor ,capacitor voltage divider and compensation capacitor (optional).
1,The reactor of the same voltage grade and capacity has smaller volume and lighter weight. Small temperature rise at rated load; Dry pouring high mechanical strength good electrical insulation beautiful and reliable.
2,Large capacity margin of frequency conversion power control box; Strong protection function; Good output waveform; Good stability; With a variety of working modes easy to operate; Single-phase 220V or three-phase 380V input power supply is common which is convenient for on-site power collection.
3,Flexible configuration. Can choose different types of reactor meet the requirements of different test products achieve a multi-purpose cost-effective.
Rated output voltage | 0~1000kV and below |
output frequency | 30~300Hz |
Resonance voltage waveform | Pure sine wave waveform distortion rate≤1.0% |
Working time | Full power continuous working time of 60min |
Quality factor | 30~90 |
Frequency regulation sensitivity | 0.1Hz |
Instability | <0.05% |
Working power supply | Single-phase 220V or three-phase 380V±10% |
Power frequency 50Hz±5% |
Serial product configuration(Application range (10kV ~ 500kV voltage grade substation electrical equipment ac withstand voltage equipment frequency 30 ~ 300Hz))
Product model name | Variable frequency source | Resonant reactor | Exciter transformer | Voltage divider | Scope of application |
TKBPXZ-50/50 | 4kW | 25kV/1A two(dry) | 4kVA(dry) | 50kV | 1000kVA and below 10kV power transformer. 10kV switch bus PT CT etc. 10 kv (300mm2) cable 1.0 km or less |
TKBPXZ-108/108 | 6kW | 27kV/1A four(dry) | 6kVA(dry) | 110kV | 31500kVA and below 35kV power transformer. 35kV switch bus PT CT etc. 10 kv (300 mm2)cable≤2km.35kV (300mm2)cable≤0.5km |
TKBPXZ-200/200 | 10kW | 50kV/1A four(dry) | 10kVA(dry) | 200kV | 50000kVA and below 110kV power transformer.110kVGIS,PT,CT etc.(Preventive test).35kV(300mm2)cable≤1.0km.10kV (300mm2)cable≤2.0km |
TKBPXZ-270/270 | 15kW | 45kV/1A Six sets of(dry) | 15kVA(dry) | 300kV | 50000kVA and below 110kV power transformer.110kVGIS,PT,CT etc..35kV(300mm2)cable≤1.2km.10kV (300mm2)cable≤3.0km |
TKBPXZ-800/400 | 30kW | 50kV/2A eight(dry); 100kV/2A four(oil-immersed) | 30kVA(dry); 30kVA(oil-immersed) | 400kV | 80000kVA and below 220kV power transformer.50000kVA and below 110kV power transformer.110kV/220kVGIS,PT,CT etc..35kV(300mm2)cable≤2.0km.110kV (300mm2)cable≤0.7km |
TKBPXZ-1600/800 | 60kW | 200kV/2A four(oil-immersed) | 60kVA(dry) | 800kV | 220kV power transformer of 80000kVA and below.50000kVA and below 110kV power transformer.500kVGIS,PT,CT etc..220kV switch ,GIS,PT,CT etc..110kV(400mm2)cable≤1.5km.220kV (400mm2)cable≤1.0km |