Model No.: TKBPXZ
Frequency regulation sensitivity: 0.1Hz
Working time: Full power continuous working time of 60min
Resonance voltage waveform: Pure sine wave waveform distortion rate≤1.0%
Production Capacity: 10
Show

Product Description

Product Description

       
        Transformer GIS SF6 switch CT/PT insulator bus bar cable bushing and others capacitive devices are the common primary electric equipments.

        The complete set of frequency conversion series resonance test equipment is mainly used for ac withstand voltage test of cross-linked cable, hydraulic generator, main transformer, bus GIS etc. 

       The complete set of frequency conversion series resonance test equipment is mainly composed of frequency conversion control power, supply excitation ,transformer reactor ,capacitor voltage divider and compensation capacitor (optional).

  

product features 

  • 1,The reactor of the same voltage grade and capacity has smaller volume and lighter weight. Small temperature rise at rated load; Dry pouring high mechanical strength good electrical insulation beautiful and reliable.

  • 2,Large capacity margin of frequency conversion power control box; Strong protection function; Good output waveform; Good stability; With a variety of working modes easy to operate; Single-phase 220V or three-phase 380V input power supply is common which is convenient for on-site power collection.

  • 3,Flexible configuration. Can choose different types of reactor meet the requirements of different test products achieve a multi-purpose cost-effective.


Product Parameters

technical parameter

Rated output voltage0~1000kV and below
output frequency30~300Hz
Resonance voltage waveformPure sine wave waveform distortion rate≤1.0%
Working timeFull power continuous working time of 60min
Quality factor30~90
Frequency regulation sensitivity0.1Hz
Instability<0.05%
Working power supplySingle-phase 220V or three-phase 380V±10%
Power frequency 50Hz±5%

Serial product configuration(Application range (10kV ~ 500kV voltage grade substation electrical equipment ac withstand voltage equipment frequency 30 ~ 300Hz))

Product model nameVariable frequency sourceResonant reactorExciter transformerVoltage dividerScope of application
TKBPXZ-50/504kW25kV/1A two(dry)4kVA(dry)50kV1000kVA and below 10kV power transformer. 10kV switch bus PT CT etc. 10 kv (300mm2) cable 1.0 km or less
TKBPXZ-108/1086kW27kV/1A four(dry)6kVA(dry)110kV31500kVA and below 35kV power transformer. 35kV switch bus PT CT etc. 10 kv (300 mm2)cable≤2km.35kV (300mm2)cable≤0.5km
TKBPXZ-200/20010kW50kV/1A four(dry)10kVA(dry)200kV50000kVA and below 110kV power transformer.110kVGIS,PT,CT etc.(Preventive test).35kV(300mm2)cable≤1.0km.10kV (300mm2)cable≤2.0km
TKBPXZ-270/27015kW45kV/1A Six sets of(dry)15kVA(dry)300kV50000kVA and below 110kV power transformer.110kVGIS,PT,CT etc..35kV(300mm2)cable≤1.2km.10kV (300mm2)cable≤3.0km
TKBPXZ-800/40030kW50kV/2A eight(dry);
100kV/2A four(oil-immersed)
30kVA(dry);
30kVA(oil-immersed)
400kV80000kVA and below 220kV power transformer.50000kVA and below 110kV power transformer.110kV/220kVGIS,PT,CT etc..35kV(300mm2)cable≤2.0km.110kV (300mm2)cable≤0.7km
TKBPXZ-1600/80060kW200kV/2A four(oil-immersed)60kVA(dry)800kV220kV power transformer of 80000kVA and below.50000kVA and below 110kV power transformer.500kVGIS,PT,CT etc..220kV switch ,GIS,PT,CT etc..110kV(400mm2)cable≤1.5km.220kV (400mm2)cable≤1.0km