Earthing switch
Grounding switch
JN2-40.5 indoor high voltage grounding switch
JN2-40.5 indoor high-voltage grounding switch is suitable for 35KV and below three-phase AC 50HZ power system, it has a voltage monitoring device, its structure is simple and reliable, small operating force, easy installation and commissioning. It is usually used in 40.5KV switchgear cabinets and also can be put into use alone.
JN4-12 (G) Indoor high voltage grounding switch
JN4-12 (G) indoor high-voltage grounding switch is suitable for 12KV indoor AC metal armored withdrawable metal-enclosed switchgear and other high-voltage switchgear, it also can be used alone. It is used for grounding protection in AC 50HZ power system of 12KV and below. It has fully closed short-circuit current capability, reasonable structure, small size, flexible operation and easy installation and adjustment.
JN15-12 (24,40.5) /31.5 indoor high voltage grounding switch
JN15-12 (24,40.5) /31.5 indoor high-voltage grounding switch is suitable for 10KV, 24KV, 40.5KV and below AC 50HZ power system, it can be used for grounding protection during maintenance of high-voltage electrical equipment, and can also be used to support with various models high-voltage switchgear.
JN22-40.5 / 31.5 indoor high voltage grounding switch
JW6-252 outdoor high voltage AC grounding switch
JW6-252 outdoor high-voltage AC grounding switch (hereinafter referred to as grounding switch) is a three-phase AC 50Hz high-voltage electrical equipment, which is used to ground the bus bar and electrical equipment to be overhauled to ensure personal safety. This product can also be used as the neutral point grounding switch of the transformer. It has many advantages such as advanced structure, good electrical performance, stable and reliable mechanical performance, easy installation and commissioning, and easy operation.
JW6-40.5~252 straight-arm grounding switch
JW6-40.5
JW6-72.5
JW6-126
JW6-252
JW5A-363~1100 folding arm grounding switch
JW5A-363
JW5A-550
JW5A-800
JW5A-1100
JW9-252~1100 grounding switch
JW9-550
JW9-800
JW9-1100
No | Item | Technical parameter | |||||
1 | Rated Voltage kV | 72.5 | 123 | 145 | 245 | ||
2 | Rated Current A | 630 | |||||
3 | Rated Short Time withstand current and Time kA/s | 25~50/4 | |||||
4 | Rated Peak withstand current kA | 63~125 | |||||
5 | 1min power frequency withstand voltage (effective value) kV | To earth | 140 | 230 | 275 | 460 | |
To phase | 140 | 230 | 275 | 460 | |||
Across Isolating DS | 180 | 300 | 315 | 605 | |||
6 | Lightning Impulse wishstand voltage (peak value) kV | To earth | 325 | 550 | 650 | 1050 | |
To phase | 325 | 550 | 650 | 1050 | |||
Across Isolating DS | 405 | 650 | 750 | 1200 | |||
7 | Rated mechanical terminal load N | Level of lateral load | 750 | 1500 | 1500 | 2000 | |
Level of vertical load | 500 | 1000 | 1000 | 1500 | |||
Vertical | 750 | 1000 | 1000 | 1250 | |||
8 | Capacity and Inductive Ability (open and close) | Capacity Current A | 1 | ||||
Inductive Current A | 0.5 | ||||||
9 | Max Man Operative Moment N.M | 200 | |||||
10 | Motor Drive operating mechanism control voltage V | AC220;DC110, 220 | |||||
11 | Motor Drive operating mechanism motor voltage V | AC220, 380;DC110, 220 |