Insulating Oil Tan Delta Tester Transformer Oil Dielectric Loss Test System

2000.0 USD
Min. Order: 1 Piece/Pieces
Trade Term: FOB,CFR,CIF,DAT,FAS,DDP,DAP,CIP,CPT,EXW
Payment Terms: Paypal, L/C, D/P, D/A, T/T, WU, Money Gram
Supply Ability: 500pcs / month
Place of Origin: Shaanxi

Company Profile

Location: Xi'an, Shaanxi, China (Mainland)
Business Type: Manufacturer, Trading Company, Distributor/Wholesaler

Product Detail

Means of Transport: Ocean, Air, Land
Application: Underground
Brand Name: HS
Production Capacity: 500pcs / month
Packing: wooden cases
Delivery Date: 7 days
Show

Product Description

Insulating oil tan delta tester transformer oil dielectric loss test system

Power supply voltage: AC 220V±10%
Power frequency: 50Hz/60Hz ±1%
Measurement range:  Capacitance: 5pF ~ 200pF
Relative permittivity: 1.000~30.000
Dielectric loss factor: 0.00001~100
DC resistivity: 2.5 MΩm to 20 TΩm
Measurement Accuracy: Capacitance: ± (1% reading + 0.5pF)
Relative permittivity: ± (1% reading)
Dielectric loss factor: ± (1% reading + 0.0001)
DC resistivity: ± (10% reading)
Resolution: Capacitance: 0.01pF
Relative permittivity: 0.001
Dielectric loss factor: 0.00001
Temperature range: 0 ~ 125 °C
Temperature measurement error: ±0.5 °C
AC test voltage: 500~2200V continuously adjustable, frequency 50Hz
DC test voltage: 0 ~ 500V continuously adjustable
Power loss: 100W
Size: 500×360×420mm
Weight: 22Kg