user login

SF6 RMU

Payment Terms: FOB Ningbo
Place of Origin: Zhejiang

Company Profile

Location: Ningbo, Zhejiang, China (Mainland)
Business Type: Manufacturer

Product Detail

Model No.: HXGN(59)-40.5
Means of Transport: by sea
Brand Name: Tianan

Product Description

 HXGN¡õ40.5 SF6 RMU (hereafter referred to as Ring Main Unit))is 50 HZ Indoor three-phase AC HV Switchgear. Load switch, earthing switch and the busbar of its circuit are fitted in the metal enclosure. Besides, it is a composite apparatus adopting spring operating mechanism and SF6 gas as arc extinction medium and insulation medium. It is suitable for 40.5 kV ring main power supply or two-radiation power supply. It changes the original single radiation power supply. When power supply line fails, it can restore the circuit of transformer and enhances the reliability and use actor of power supply largely. It is specialized in trading estate or villages and towns where electricity power is largely needed. It is safety in use, easily installed, less maintenance, less in space and not influenced by the climate. It is suitable for being fitted in the combined substation. And the load switch or load switch-fuse composite apparatus inside the RMU is able to be used separately.
Product feature :
      a. It consists of switch compartment, fuse compartment, operating mechanism compartment and cable compartment(bottom frame).
      b. The switch compartment consists of function circuit (including earthing switch and load switch) and busbar among the circuits. The metal enclosure is welded 3mm cold rolled steel sheet (or corrosion resistance plate). Each function circuit includes a load switch and earthing switch. The load switch is made up of moving contact which runs vertically and the static contact at the bottom. When the switch closes, the moving contact moves down and the load switch opens. The earthing switch is made up of moving contact and static contact. When the spring runs, the earthing switch is cut in immediately. There are four rectangle pilot holes on the upper parts of the switch department and at the back of the switch. There is a inspection window on the right side of the RMU, through which"O" and "C" position of the earthing switch can be seen. Hydrostat is mounted at the back of the RMU.
       c. The load switch adopts air blast structure, which enhances the arc extinction capacity, but won't  affect the insulation of phase to phase and phase to earth. Besides both of moving contact and static contact have arc contacts, which increase the breaking times.
      d. Both of fuse switch and load switch compartment consist of the protection circuit of transformer. The HV current limiting fuse is fitted in the epoxy casting insulating closure. When the fuse melts, then firing pin will bounces out, next the load switch opens.
      e. Operating mechanism compartment is on the right side of the RMU. In each function circuit, the load switch has a manual drive ( or motor drive ) power spring operating mechanism and the earthing switch has a manual drive power spring operating mechanism. There are a closing and manual drive breaking screwing button of load switch, the on/off operating hole of earthing switch, on/off indicator light and motor drive on/off button of load switch, simulated line, condition display plate of switch, lock position on the faceplate. Both of the load switch and the earthing switch own interlock devices to prevent from incorrect manipulation.
Type designation :

 
Technical parameter:
Item
Uint
Parameter
Rated voltage
kV
40.5
Lightning impulse withstand voltage(peak value)
Phase to earth£¬phase to phase
kV
185
Isolating distance
kV
215
1min
power frequency withstand voltage
Phase to earth, phase to phase
kV
95
Isolating distance
kV
118
Load switch
Rated current
A
630
Rated short time withstand current (2s)
kA
20
Rated short time withstand current(peak value)
kA
50
Rated short circuit making current (peak value)
kA
50
Mechanical endurance
times
5000
Busbar side of earthing switch
Rated short time withstand current(2s)
kA
20
Rated peak withstand current(peak value)
kA
50
Rated short circuit making current (peak value)
kA
50
Mechanical endurance
times
2000
Earthing circuit
Rated short time withstand current(2s)
kA
17.4
Rated peak withstand current(value)
kA
43.5
Fuse
Rated current
A
50
Rated short circuit breaking current
kA
31.5
Protection degree
Main circuit (load switch, earthing switch)
 
IP5X
Fuse, cable connecting piece
 
IP4X
Fuse compartment, mechanism compartment
 
IP3X
Ordering notice :
      Please provide the followings while ordering ;
      a. The product name, pattern, size, quantity, rated voltage of fuse and delivery time ;
      b. Pareto diagram and layout plan of UMU ;
      c. Spare part needed (such as gas-filling device and deflation device) ;
      d. Cubical colour ;
      e. If any special request, please negotiate with us
Post Buying Request