Product Description

HUAWEI R48100G1 48V 6000W Rectifier Module

 

R48100G1 Short Brief: The R48100G1 is a digital control 3-phase rectifier with the maximum output power being 6000W. It converts 260~530VAC input voltage to 53.5VDC output voltage. The output voltage can be adjusted by the host. It performs comprehensive protection functions, supports soft start, and produces low noise. With the latest power monitoring technology, states of the rectifier and load are monitored in real time. Multiple rectifiers can be paralleled.

 

48V 6000W Rectifier Features:

1) Input voltage range: 260~530VAC
2) Operating temperature range: -40 ºC to +75 ºC (output derating above 45ºC)
3) Total harmonic distortion (THD): ≤ 5%
4) Digital control mode
5) Hot swap
6) Supports intelligent electric meter
7) Supports CAN communication
8) Supports LED display
9) Supports voltage and current adjustment
10) Passes the TUV,CE,UL certifications and gets the CB certificate

HUAWEI R48100G1 120A Rectifier Specification

 

R48100G1 Weight: 6kg
Dimensions: 43 x 238 x 378mm
R48100G1
HUAWEI R48100G1 48V 6000W rectifier module

Notes


1. We will ship the item in 3-5 work days after the payment arrive.
2. We will usually ship the item to Worldwide by FedEx/ UPS/DHL.
3. Buyer's responsibility to pay customs fees, duties, import taxes, shipping charge
And related charges.
4. We accept the payment through T/T, Paypal, and Western Union.
5. The pictures show you one of the items in stock. But the exact one may be sold before your bidding. So it may not the exact one which you will receive.

 

Specifications

 

Product Type

R48100G1

 

Basic Specifications

Dimension

238 mm(W) × 378 mm(D) × 43 mm(H)

Weight

≤ 6.0 kg

Cooling

Forced air cooling (Built-in fan)

 

 

 

 

Input Feature

Input Voltage

260 to 530 Vac

AC Input Mode

380 Vac three-phase three-line

Frequency

45 to 66 Hz, rated: 50/60 Hz

Maximum Input Current

≤ 13 A

Power Factor

≥ 0.99 (Vin: 360 Vac, 380 Vac, 415 Vac, three-phase balance)

THD

≤ 5% (Vin: 308 to 480 Vac)

 

 

 

 

 

Output Feature

Efficiency

> 96% Max

Output Voltage

43.2 to 58 Vdc, rated voltage: 53.5 Vdc

Output Power

6000W (304 to 530 Vac )

Ripple and Noise

< 200 mV pk-pk, 20 M bandwidth, < 2 mV rms psophometric

Hold-up Time

> 10 mS at 6000 W , output voltage > 42 V

Output Regulated Voltage Precision

≤ 0.6% Vo from no load to full load

Current Share

±5% output rated current from 10% to 100% load

 

 

Environmental Specifications

Operating Temperature

-33 ℃ to +75 ℃ (non-derating below 45 ℃), ETS EN 300-019

Storage Temperature

-40 ℃ to +75 ℃; ETS EN 300-019

Relative Humidity

5% to 95% (non-condensing), ETS EN 300-019

Altitude Range

≤ 4000 m (If the altitude is within the range of 2000 m to 4000 m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200 m)

 

 

 

 

 

Protection

Input Overvoltage Protection

Protection point: 530 to 550 Vac

Input Under-voltage Protection

Protection point: < 260 Vac

Output Over-voltage Protection

58.5 to 60.5 Vdc (can be set by monitoring unit)

Output Short Circuit Protection

A long term short circuit is allowed. After the fault is rectified, the rectifier will restore automatically

Over-temperature Protection

Protection point: > 75 ℃

Reliability

MTBF

≥ 500,000 hours (Telcordia SR-332 issue2 Method 1 at 25 ℃)

Audible Noises

Specification

≤ 45dB (25 ℃, full load); sound presure@1m distance, ISO3744

 

 

Safety/EMC/ Lightening Protection

Safety Certification

Passed TUV, CE, UL certifications; got the CB certificate; complies with UL60950-1, IEC60950-1,

EN60950-1, CAN/CSA C22.2 No. 60950 -1

Isolation

Input to output: 4242 Vdc; input to earth: 2121 Vdc; output to earth: 707 Vdc

EMC

EN55022 Class B, EN55024, EN61000-3-2, EN61000-3-3, ETSI EN300 386, ETSI EN301489, ITU-T K.20

Lightening protection

Common model (input to earth) / differential model (input to input): 5KA (8/20uS, ITU-T K.44)