      18 Stranded Wire Bare Aluminum Conductor For Electrical Power Distribution

 

   Product Description
 
Bare conductor AAC AAAC ACSR for outdoor overhead power transmission has been widely used in power transmission lines with various voltage levels.
1. Applications

Bare conductor AAC AAAC ACSR for outdoor overhead power transmission has been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.

 

2. Service Performance

Bare conductor AAC AAAC ACSR for outdoor overhead power transmission

(1). The permissible long-time operating temperature for aerial conductor is 70oC.

(2). Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.

(3). When connecting conductors,the conductor beside the connecting tube cant be prominent.Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.

(4). Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.

 

3. Product Performance

Bare conductor AAC AAAC ACSR for outdoor overhead power transmission

(1). The electrical performance of AAC and ACSR is indicated in DCΩ/km(20oC).The resistivity of the hard aluminum wire for stranded wires is not greater than 28.264 nΩ. m of international standard value.

(2). The rated tensile strength of AAC is denoted with the result of total cross-section of all aluminum conductors multiplied by min.tensile of corresponding size specified in the standard for aluminum wire.

(3). The rated tensile strengh of ACSR is denoted with sum of all aluminum conductorstensile strength and steels tensile strength.

a. The tensile strength of all aluminum conductors is denoted with the result of all cross-sections of aluminum conductors multiplied by min.tensile strength of corresponding size specified in the standard for aluminum wire.

b. The tensile strength of all steel wire is denoted with the result of all cross-sections of steel wires multiplied by the stress at 1% elongation of corresponding size specified in the standard for steel wire.

 

 

 

 

 

 

 

 

4. Material Standard

Bare conductor AAC AAAC ACSR for outdoor overhead power transmission

(1). The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048- 1997(equivalent to IEC 60889:1987).

(2). The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.

(3). Production can be arranged according to customers requirements for material standard,etc.

Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced

 

5. Chinese Standard

 

Post Buying Request
Code name

Aluminum

Area

Stranding&

Wire Diameter

Approx

Overall

Diameter

Approx

Weight

Breaking

Load

DC

Resistance

Al Steel
AWG mm2 No./mm No./mm mm Kg/km KN Ohm/km
Turkey 6 13.30 6/1.68 1/1.68 5.04 53.75 5303 2.157
Swan 4 21.18 6/2.12 1/2.12 6.36 85.57 8302 1335
Swanate 4 21.12 7/1.96 1/2.61 6.53 99.56 10642 1352
Sparrow 2 33.59 6/2.67 1/2.67 8.01 135.70 12653 0.854
Raven 1/0 53.52 6/3.37 1/3.37 10.10 216.20 19455 0.536
Quail 2/0 67.32 6/3.78 1/3.78 11.30 272.00 23529 0.426
Pigeon 3/0 85.14 6/4.25 1/4.25 12.80 344.00 29417 0.337
Penguin 4/0 107.20 6/4.77 1/4.77 14.30 433.40 37055 0.268
Waxwing 266800 135.00 18/3.09 1/3.09 15.50 430.50 30519 0.213
Merlin 336400 170.20 18/3.47 1/3.47 17.40 542.90 38487 0.169
Linnet 336400 170.60 26/2.89 7/2.25 18.30 689.90 62918 0.169
Hawk 477000 241.6 26/3.44 7/2.67 21.80 975.50 86011 0.120
Dove 556500 282.6 26/3.72 7/2.89 23.6 1142.00 100838 0.1030
Peacock 605000 306.2 24/4.03 7/2.69 24.2 1159.00 95861 0.0948
Drake 795000 402.5