user login

Pmg Alternator Coupled with Diesel Engine

2599.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB
Payment Terms: Paypal, T/T, WU, Money Gram
Supply Ability: 40000
Place of Origin: Anhui

Company Profile

Location: Hefei, Anhui, China (Mainland)
Business Type: Manufacturer, Trading Company, Distributor/Wholesaler, Service

Product Detail

Model No.: TCU318
Means of Transport: Ocean, Air
Protection Class: IP22/23/IP44/IP55
Voltage: 190V~690V
Insulation Class: H Class
Bearing: Single and Double Bearing
Excitation: Self-excited and PMG
Phase: Three phase
Special Feature: Flat Copper Wire
Certificate: ISO 9001, ISO14001 and CE
Advantage: Short and compact
Type: 4 Pole
Production Capacity: 40000
Packing: Wood Case
Delivery Date: A week
Show

Product Description

Pmg Alternator Coupled with Diesel Engine


Duty rating: S1
Number of poles: 4
Winding pitch: 2/3
Powers: up to 4000kVA
Terminal: 6 and 12 leads
Frequency: 50Hz to 60Hz
Voltage regulation: +/- 0.5%
Power factor : 0.8 lagging
Speed: 1500rpm or 1800rpm
Low voltage: 110V to 690V 
Maximum unbalance load: 25%
High voltage: 3300V to 13800V 
Overload: 10% for 1 hour in every 12 hours
Direction of rotation: CW from drive end
Harmonic distortion factor: < 3% for three-phase
Degree of Protection: IP22 (IP23, IP44, IP54 on request)
Short circuit withstand capability: 3 times at full load current 


Advantages:

1) Strong and rigid frame structure ensuring less vibration when assemble with the diesel generator set.
2) The generator cooling wind path is shorten, ensuring good heat dissipation effect and lower temperature.
3) Provide substantial cost saving when assembling to any G-Drive engines, especially when assembling with a canopy enclosure or soundproofing system.

Patented Technology:


The stator laminations and the soft-end band fixing structure of stator coil ends with national patent technology
The enameled flat/rectangular copper wires and novel design rotor winding inter-turn insulation structure with national patented technology




Rotor's design using the innovative technology, using all 100% copper flat wire and gained two patents. 
Advantage 1 : Increase pole coil's resistance to voltage shock and increase generator's life and reliability.
Advantage 2:  Decrease shock to rectifier bridge and increase its life and reliability.
Advantage 3 : Increase exciter reaction speed,and decrease AVR's output current to improve it's  sensitivity and life time.


Altitude
The rated power refers to installations up to 1000 meter above sea level. For applications over this altitude, the following power correction factor must be applied.
Altitude (m.a.s.l)<1000<1500<2000<2500<3000<3500
K Factor10.960.930.90.86refer
Ambient Temperature
The rated powers refer to installation with ambient temperature of 40°C. For applications different from 40°C, the following power correction factor must be applied.
Ambient Temperature30°C35°C40°C45°C50°C55°C
K Factor1.04110.960.930.9
Power factor
The nominal power factor is 0.8 lagging. For application with power factor value different from 0.8, the following correction factor must be applied.







Power Factor0.80.70.60.50.30
K Factor10.930.880.840.820.8
Power variation according to temperature and altitude
For applications with ambient temperature different from 40°C and altitude more than 1000 m.a.s.l, the following power correction factor must be applied.
Altitude (m.a.s.l)25°C40°C45°C50°C55°C
< 10001.0910.960.930.91
1000 - 15001.010.960.920.890.87
1500 - 20000.960.910.870.840.83
2000 - 30000.90.850.810.780.76


Main Raw Material :
1. Copper wire has passed UL certified class 200.
2. Shaft using 45 Steel
3. Bearing uses TWG brand (Can be pointed brand)
4. Fan is cast aluminium 
5. End shield uses HT 200. (The best casting material)


Product List:


ModelLeadKVA/KW temperature rise/Ambinetn Temperature(125o /40o)
Continuous Duty 50HZ/1500rpm 400V

    KVA              KW

Efficiency full load pf:08Continuous Duty 60HZ/1800rpm  400V

     KVA              KW

Efficiency full load, pf:08
TCU188A ~ TCU188F 1220~42.516~3482.6~87.322.5~4918~3982.3~87.4
TCU 228A~

TCU 228N

1245~16036~12886.9~91.552.5~18442~14787.3~91.8
TCU 288A~

TCU 288K

12165~325132~26091.6~93.6191~375153~30091.4~93.2
TCU 318A~

TCU 318D

12350~450280~36093.5~94406~525325~42093.3~94
TCU 368A~

TCU368G

12500~750400~60093.9~94.7581~875465~70094~94.7
TCU 428A~

TCU 428F

6800~1400640~112094.8~95.6938~1625750~130094.8~95.6
TCU 468A~

TCU 468F

61500~22501200~180095.8~96.21750~25631400~205095.8~96.3
TCU 528A~

TCU 528B

62500~27502000~220096.1~96.32875~31502300~252096.2~96.4
TCU 568A~
TCU 568C
63000~35002400~280096.5~96.63428~40002750~320096.6~96.7






Post Buying Request