Protective Relays LR2-D Protection Relay

Company Profile

Location: Shanghai, China (Mainland)
Business Type: Manufacturer
Main Products: Circuit Breaker, Circuit Breakers, Residual-current Device, Rcd, Rccb

Product Description

Protective Relays LR2-D Function EBS1TR Series thermal overload relays apply to circuit of AC 50Hz or 60Hz, rated voltage to below 660V and rated current 0.1~93A for AC Motor overload and single phase protection during long time or intermittent long time service, which can also protect three phase serious imbalance and long starting time of motor or long time operation, can also be used for corresponding AC contactor for electromagnetic starter. Technical Parameter Model NameEBS1TR protection relayStandardIEC60947-4-1Setting current multiple1.05, 1.2, 1.5, 7.2Rated current In(A)25 36 93AmpRated voltage Un(V)230V 240V 380VFrequency of coil50Hz, 60Hz, 50/60HzNumber of auxiliary contact10 /01 /11Protection gradeIP20Pollution grade3Features ●EBS1TR has innovative, elegant model and small installation area, functions such as temperature compensation,action indication, automatic and manual reset, stop with steady and reliable performance.●Can be connected with contactor or installed separately●Action CharacteristicsOverload protection Phase failure protection Applicable Working Ambient temperature-5~+40℃, the average value cannot exceed to +35℃ within 24hAltitude≤2,000mRelative humidity≤95%Pollution levelII.Installation locationMount on the place where has no obvious vibration or impact