user login

Electrical ABC Aerial Bundled Cables Three Core For Under Ground / Villages Electrification

Place of Origin: Zhejiang

Company Profile

Location: Shanghai, China (Mainland)
Business Type: Manufacturer

Product Detail

Model No.: ABC-0.6/1 KV-AL/PVC 3 Cores

Product Description

 

Electrical ABC Aerial Bundled Cables Three Core For Under Ground / Villages Electrification

 

 

Product name Aerial Bundled Cable Overhead cable with Aluminum conductor

NFA2X NFC33-209, TS HD 604 S1

NFC33-209, TS HD 604 S1, GB/T 12706.1-2008.

CE, CCC, KEMA /

0.6/1kV, suitable for underground burying

 

Constructions

Conductor: Plain circular stranded aluminum conductor, conforms to IEC 60228 class 2

Insulation: PVC

Note: Insulation color as per standards or at request

Applications

ABC cable especially used at areas where the cost of under ground networks is expensive and also for electrification of rural areas like villages .

Standards

International: NFC33-209, TS HD 604 S1

China: GB/T 12706.1-2008

Other standards such as BS,DIN and ICEA upon request

 

Technical data

Rated voltage: 0.6/1kV

Max. Conductor Temp.: normal (90), short circuit no more than 5 s (250 when section-area below 300mm2,)

 

Certificates

CE, RoHS, CCC, KEMA and more others at request

 

 

 

 

Schedule of technical particulars

 

Phase conductor                      
Nominal cross-sectional area mm² 16 16 25 35 50 70 95 120 150 185
Number of cores   1 3 3 3 3 3 3 3 3 3
Minimum number of wires   6 6 6 6 6 12 15 15 30 30
Nominal insulation thickness mm 1 1 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0
Diameter of insulated core mm 6.8 6.8 8.5 9.5 11.2 13.0 15.1 16.6 18.4 20.6
Max. DC resistance at 20 ohm/km 1.91 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164
Current rating at still wind, ambient A 61 61 84 104 129 167 209 246 283 332
temperature=30
Conductor temperature=75                      
Messenger conductor                      
Nominal cross-sectional area mm² 25 25 25 25 35 50 70 70 95 120
Minimum number of wires   6 6 6 6 6 6 12 12 15 15
Nominal insulation thickness mm 1.2 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.6 1.6
Diameter of insulated core mm 8.5 8.5
Post Buying Request