Place of Origin: | Zhejiang |
---|
Location: | Shanghai, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Model No.: | VV 1~5C, CU/PVC/PVC 600/1000V |
---|
Custom Copper Conductor PVC Insulated Cables Low Voltage CE IEC Standard
Installation
1. The installation temperature should not over 20, If the ambient temperature is lower than 0, the cable should be preheated.
2. The bending radius of cable should not less than 8 times.
3. After installantion, the cable should with stand voltage test for 15min. 3.5kv D.C.
Applications
PVC Insulated Cable is used as power distribution and transmission line at rated voltage 0.6/1KV.
Construction
Conductor | Copper/Aluminum Conductor as per IEC 60228 |
≤6mm2 solid (class 1) | |
6mm2 stranded (class 2) | |
≥50mm2 shaped conductor | |
Copper: flexible conductor(class 5) optional. | |
Insulation | PVC(polyvinyl chloride) rated at 75,many color optional |
Metallic Screen optional | Copper tape or copper wires braiding optional |
Armored optional | Aluminum wire or stainless steel tape for single core cable, Steel wire or steel tape for multi core cable |
Sheath | PVC or FR-PVC type ST2 to IEC 60502, black or red or customization |
Standards
International: IEC 60502, IEC 60228, (IEC 60332-3 for FR-type only)
China: GB/T 12706, (GB/T 18380-3 for FR-type only)
Other standards such as BS,DIN and ICEA upon request
Technical parameter
Cross section of conductor | Thickness of insulation | Thickness of Sheath | Approx.cable diameter | Max.resistance of conductor at 20 (Cu) | Test Voltage(AC) |
mm2 | mm | mm | mm | ohm/km | KV/5min |
1.5 | 0.8 | 1.4 | 6.1 | 12.1 | 3.5 |
2.5 | 0.8 | 1.4 | 6.5 | 7.41 | 3.5 |
4 | 1.0 | 1.4 | 7.4 | 4.61 | 3.5 |
6 | 1.0 | 1.4 | 7.9 | 3.08 | 3.5 |
10 | 1.0 | 1.4 | 9.2 | 1.83 | 3.5 |
16 | 1.0 | 1.4 | 10.3 | 1.15 | 3.5 |
25 | 1.2 | 1.4 | 12.0 | 0.73 | 3.5 |
35 | 1.1 | 1.4 | 13.2 | 0.524 | 3.5 |
50 | 1.4 | 1.4 | 14.9 | 0.387 | 3.5 |
70 | 1.6 | 1.4 | 16.7 | 0.268 |
|