Min. Order: | 1 Piece/Pieces |
---|---|
Trade Term: | EXW |
Payment Terms: | T/T, WU |
Supply Ability: | 1000pcs per week |
Place of Origin: | Guangdong |
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Model No.: | HP1101B |
---|---|
Means of Transport: | Ocean, Air, Land |
Application: | Telecommunications |
Phase: | Single Phase |
Type: | On-line |
Protection: | Unbalanced Loads |
Brand Name: | Shangyu |
Weight: | 12kg |
Output Voltage: | 220 x (1±2%)VAC |
Nominal capacity: | 1kva/800w |
Input voltage: | 115-300V |
Input power factor: | >0.98 (Full load) |
Input Freqiency: | 40-70HZ (Adjustable) |
Output Frequency: | 50±0.2Hz |
Battery Type: | Maintenance-free Valve regulated lead acid(VRLA)battery |
Battery nominal voltage: | 24V |
Charging current: | 1.0A |
Safety: | IEC61000, IEC62040, GB7260,GB4943 |
Certification: | TLC/CQC/CE |
Production Capacity: | 1000pcs per week |
Packing: | Carton |
Delivery Date: | 15 days |
Main Features
Double Conversion Design
Space saving
DSP Technology
Environment Friendly
Active input power factor correction(PFC)
Wide range of input voltage and frequency
Energy saving
Emergency Power Off (EPO)
The load PFC is 0.8
Intelligent Battery Management
Full protection function
Smart RS232 communication port;
External SNMP, CMC or Dry contacts (optional)
High reliability and performance
Specifications
Model | HP1101B | HP1102B | HP1103B | |
Capacity | 1KVA/800W | 2KVA/1600W | 3KVA/2400W | |
Norminal voltage | 220VAC Single phase grounding | |||
Norminal frequency | 50Hz | |||
Input | ||||
Voltage Range | 115-300VAC | |||
Frequency Range | 50Hz:(46-54Hz) | |||
Power Factor | 0.99 | |||
Output | ||||
Voltage Precision | 220±2% | |||
Frequency Precision | 50±0.2Hz | |||
Power factor | 0.8 | |||
Harmonic Distortion | Linear load<3% Non-linear<6% | |||
Overload Capability (AC 25°C) | 105%±5% <load≤150%±5% Transfer to bypass and Alarming after more than 1min; | |||
150%±5%<load<200%±5% Transfer to bypass and Alarming after more than 300ms; | ||||
Transfer time | 0 ms(AC mode↔Battery) | |||
<4 ms(AC mode↔ Bypass) | ||||
Battery | ||||
DC Voltage | 24VDC | 48VDC | 72VDC | |
Charging current | 1A | |||
Backup Time(Full Load) | PF=0.8 ≥ 4.5min ; PF=0.9 ≥ 3min | |||
Panel Display | ||||
LED indicators | inverter, bypass, battery ,electricity ,load ,AC | |||
Communication port | Smart RS232, SNMP (Optional) , AS400(Optional),CMC(Optional) | |||
Working Environment | ||||
Temperature | 0°C-40°C | |||
Relative Humidity | 20%-90%(non-condensing) | |||
Storage Temperature | -25°C~55°C | |||
Elevation | <1000m | |||
Noise Level | <55dB | |||
Physical Characteristic | ||||
Weight(KG) | N.W | 9.9 | 17.7 | 23.2 |
Dimensions: ( W x D x H ) | 144×345×229 | 190×393×328 |