Silicon Rubber Zinc Oxide Lightning Arrester 33KV Surge Diverter for Transformer Protection

Place of Origin: Zhejiang

Company Profile

Location: Hangzhou, Zhejiang, China (Mainland)
Business Type: Manufacturer

Product Detail

Model No.: YH10W5-33/90

Product Description

Silicon Rubber Lightning Arrest , Polymer Surge Diverter Protect for Transformer

 

Description:

 

Polymer surge arrester is a device to protect electrical equipment from over-voltage transients caused by external (lightning) or internal (switching) events. Also called a surge protection device (SPD) or transient voltage surge suppressor (TVSS), thisclass of device is used to protect equipment in power transmission and distribution systems. (For consumer equipment protection, different products called surge protectors are used.) The energy criterion for various insulation material can be compared by impulse ratio, the surge arrester should have a low impulse ratio, so that a surge incident on the surge arrester may be bypassed, to the ground instead of passing through the apparatus.

 

Specifications:

 

Type YH10W5-33/90
Rated voltage---------kV 33
MOCV ----------------kV 27.5
Nominal Current-------kV 10
Residual voltage of steep impulse----at 5kA(kV) 97.5
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) 90
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) 68.7
1mA D.C reference voltage (kV) 46.7
Line discharge level 1
2mS long duration impulse current A 400
4/10µS High current impulse kA 100
Lightning impulse withstand kV 200
Power frequency voltage withstand(dry/wet)kV 70
0.1S TOV--------------kV 39.6
1S TOV----------------kV 37.95
10S TOV---------------kV 36.3
1200S TOV-------------kV 33
Creepage distance ----mm 1082
Material employed in series non-linear resistor Zinc Oxide

 