2000 Cycle Life 12V40Ah UPS Replacement Battery With BMS For Back Power Supply
Cells parameters :
Item | Rated Value | Remark | |||
Battery | 1 | Rated Capacity | Rated Capacity | 20Ah | Discharge Current: 0.5C(10A) |
Min Capacity | 20Ah | ||||
2 | Impedance | ≤5m | |||
3 | Rated Voltage | Average Voltage 3.2V 3.2V |
Battery pack specification :
Configuration | 12V(2 parallel 4 series) | |||||||
| Rated Capacity | Rated Capacity | 40Ah | Discharge Current: 0.5C(20A) | ||||
Min Capacity | 40Ah | |||||||
Rated Voltage | Average Voltage 12.8V | |||||||
Impedance | ≤50m | |||||||
Discharge Cut off Voltage | 8.0V | |||||||
Charge Voltage | 14.6V | |||||||
Max Charge Voltage | 15.0V | |||||||
Charge conditions | Standard charge current | Charge Current: 0.2C(8A) | ||||||
Rapid Charge current | Charge Current: 0.5C(20.0A) | |||||||
Instantaneous Charge current | Charge Current: 1.0C(40.0A) | |||||||
Discharge conditions | Standard Discharge current | Discharge Current: 0.5C(20A) | ||||||
Rapid Discharge current | Discharge Current: 2.0C(80.0A) | |||||||
Instantaneous Discharge current | Discharge Current: 3.0C(120.0A) | |||||||
| Working Temperature | Charge | 0~+45 | |||||
Discharge | -20~+60 | |||||||
| Storage Temperature | 1 month | -20~+45 | Recommended Storage Temperature is 20 when transport. | ||||
≥ 1 month | -10~+35 | |||||||
Initial load | 50%-60% |
Each battery pack of Soundon with the protection board in below function to manage the battery cell and battery pack :
Over-Charge Voltage Protection (OVP) |
Over-Charge Voltage Protection Release (OVPR) |
Over-Discharge Voltage Protection (UVP) |
Over-Discharge Voltage Protection Release (UVPR) |
Over-Current Discharge Protection (OCDP) |
Over-Current Protection Delay Time (OCPDT) |
Over-Discharge Protection Release |
Over-Current Discharge Protection Release |
Short circuit current protection |
Short circuit current protection delay time |
Short circuit protection Release |
Discharging Temperature |
Discharging Temperature Protection Release |
charging Temperature |
charging Temperature Protection Release |
Soundon battery advantage :
Certification :
Shipment :
The battery should be packed in cartons under the condition of half capacity 20-50% for shipment. The violent vibration,impaction or squeezing should be avoided in the transport process; neither is exposed in the sunlight nor rain. The batteries shall be shipped by normal transportation such as by road, by train, by ocean or by air.
Storage :
The battery storage shall be in the clean and dry ventilation room at the temperature of -535 and shall keep out of fire or heat and avoid touching corrosion elements. The batteries shall be charged every 6 months during storage
After sales Services :
1. 24 months product warranty period
2. Free logistic services
3. Quick Reply your in 24 working hours