Piping Hfc-227ea Fm200 Fire Extinguishing System For One Zone
parameter:
No. | specification | Technical Parameter | |
1 | Filling pressure | 4.2Mpa | 5.6Mpa |
2 | Scale of Protective region for one zone | area:max single-zone is 800m² volume:max single-zone is 3600m³ | |
3 | Spraying time | ≤10s | |
4 | Filling density | ≤950kg/m3 | ≤1080kg/m3 |
5 | power | DC24V/1.6A | |
6 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20) | |
7 | Condition of reserving room for container | temperature: -10~50, relative humidity: ≤97% | |
8 | max working pressure | 5.3Mpa | 8.0Mpa |
9 | min working pressure | 4.2Mpa | 4.6Mpa |
Applications:
1. Clean gas, colorless and tasteless and non-corrosive
2. Electric insulation, utilization for extinguishing of electrical combustion
3. No residue and pollution inside protection zone
4. No damage to ozone layer
Competitive Advantage:
1. Management of multiple zones
2. Efficient fire protection in big region
3. Less occupation in fire-controlled space
4. Relatively cheap price than cabinet or hanging type if zone is big and multiple
Composition:
1. Mechanical parts: cylinder with container valve, frame for cylinder group, driving cylinder, frame for driving device, high pressure hose etc. It is mainly used for storing fm200 agent
2. Electrical parts: smoke detector, heat detector, bell etc.
3. Pipe fittings: conduit, connector, elbow, flange etc.
Attention:
1. Choice for storage room, including ambient environment and volume
2. Design of pipeline, including placement of conduits and connection
3. Installation, integration of each parts and connection between parts