1. Nominal Power Capacity: Volt-Amps/Watts(VA/W) 6000VA/4200W 10000VA/7000W
2. Input
Nominal Voltage (Single): 220Vac
Voltage Range: 176-300Vac
Frequency Range: 46.5-55Hz
Power Factor: ≥0.95 ≥0.97
3. Output
Voltage Range: 220V± 2%
Frequency Synchronized: 46.5-55Hz or 50Hz± 0.2Hz(Line mode)50Hz0.2Hz(Battery mode)
Wave-form: Sinewave
Distortion: ≤3%(full linear load) ≤4%(full linear load)
Overload Capability: 108%-150% inverter mode for 10 minutes
≥130% by pass mode for 1 minute
4. Crest Ratio: 3: 01
5. Battery
Type: Sealecd Lead -Acid, Maintenance Free
Capacity: 12V/7AH*20PCS 12V/7AH*40PCS
6. Transfer time: 0ms; 2.5ms typical from inverter to bypass and vice versa
7. Battery mode: Alarm beeps every four seconds, every second if battery low Overload: Alarm beeps two for every second
Fault: Alarm beeps continuously
8. Acoustic Noise: At 1 meter distance 45dBA 50dBA
9. Communications: DB-9 Connector RS232 Serial Interface; Power monitoring and unattended systems shutdown via software
10. Applications: Servers Data-Center, Critical network, Sensitive electronics equipment, Telecom