user login

Transformer Turns Ratio Tester

2.0 USD
Min. Order: 1 Set/Sets
Payment Terms: Paypal, L/C, D/P, D/A, T/T, WU, Money Gram
Supply Ability: 500Sets/per Month
Place of Origin: Chongqing

Company Profile

Location: Chongqing, China (Mainland)
Business Type: Manufacturer, Trading Company

Product Detail

Model No.: GDBC-901
Means of Transport: Ocean, Air, Land
Turn Ratio Tester: Transformer Tester
High accuracy Tester: 80V RS232 Turn Ratio Tester
Production Capacity: 500Sets/per Month
Packing: Wooden Case
Delivery Date: 10days
Show

Product Description

GDBC-901 Transformer Turns Ratio Tester

Introduction:

The voltage ratio measurement for three or singe phase transformer

The group vector measurement for three phase transformer.

The polarity measurement for single phase transformer or CT/PT

Voltage ratio error calculation

Current transformer ratio measurement

Excitation current measurement in ratio testing

Reproduction the AC test voltage from power source to reduce the effects of bad power source

Save the test results in the memory internal the tester

Print the test results by micro printer

Reverse connection detect unit to prevent the high voltage injected to operator

Over current protection unit integrated in software and hardware

Upload the test results to PC by RS232 and make word report by software

Specifications:  

Ratio measurement range

 1~10000

Group measurement

 1~12

Phase measurement error

 1 degree

Ratio measurement error

 1~2000 ± 0.2%RDG

 2000~10000 ± 0.5%RDG

Test voltage

 0~80V

Power supply

 AC220V ± 10%, 50Hz/60Hz

Size

 400´350´200 mm3

Weight 7kg Humidity

 ≤85%RH


Post Buying Request