Place of Origin: | Zhejiang |
---|
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Prepaid Electricity Meters, STS Prepaid Meters, Wireless Electricity Meter |
Model No.: | CA368-E |
---|
Short Cover Commercial Electric Meter Wireless Smart Meters For Electricity
The CA368-E is a standalone residential, light commercial credit meter designed to meet a various range of customer needs across a diverse wide ranging markets. With a reputation for high quality, Calin has created a cost effective electricity meter for residential and light commercial applications that provides an extensive variety of features making it suitable for many installation purposes.
This cost effective metering solution can reduces total cost of ownership and management costs through enhanced functions and high quality design.
Features
a) Active and reactive measurement
b) Accuracy up to Cl 1 resp. Cl B (MID) [active energy] and Cl 2 [reactive energy]
c) Wide range measurement from starting current to maximum current
d) Up to 4 rates and 108 holiday settings
e) Large liquid crystal display with max. 8 digits for the value and high resolution
f) Buttons for display control, MD reset, billing resetting and advance
g) Optical and electrical interfaces
h) Optical test outputs
Specifications:
Electrical parameters |
|
---|---|
Nominal voltage Un |
3x 220/230/ 240V |
Limited voltage |
60%~120%Un |
Frequency |
50/60Hz+5% |
Basic current(Ib) |
5A |
Maximum current(Imax) |
100A |
Starting current(Ist) |
30mA |
Active energy constant |
400imp/kWh |
Accuracy |
|
Active energy to IEC6205321 |
Class1.0 |
Reactive energy to IEC6205323 |
Class2.0 |
Power Consumption |
|
Power consumption in Voltage circuit |
<2W <8VA |
Power consumption in current circuit |
<1VA |
Temperature range |
|
Operation meter |
25 to+70 |
Storage |
40 to+85 |
|
|
Insulation strength |
|
AC Insulation strength |
4kV at 50Hz during 1min |
Impulse voltage 1.2/50μs mains connections |
8kV |
|
|
Electro Magnetic Compatibility |
|
Electrostatic discharges |
|
Contact discharge |
8kV |
Air discharge |
16kV |
Electromagnetic RF fields |
|
27MHz to 500MHz typical |
10V/m |
100kHz to 1GHz typical |
30V/m |
Fast transient burst test |
4kV |
Mechanical requirements |
|
Protection Rating |
IP54 |
Insulation Classification |
Protective Class II |
Maximum cable size |
10 mm |