user login

Transformer Sweep Frequency Response Analysis ( SFRA ) Test Set

Min. Order: 1 Set/Sets
Payment Terms: L/C, T/T, WU
Supply Ability: 1000/month
Place of Origin: Chongqing

Company Profile

Location: Chongqing, China (Mainland)
Business Type: Manufacturer, Trading Company
Main Products: Oil Purifier, Oil Tester

Product Detail

Model No.: GDRZ-902
Usage: Others
Power: Electronic
Brand Name: gold
Two different sweep modes: Linear sweep, Section sweep
Production Capacity: 1000/month
Packing: Veneer case
Delivery Date: within 15 days
Show

Product Description

Product Description

  • The structure and reference of the transformer is fixed after been made, Therefor, the frequency response of each winding will be almost the same normally.

  • Some case such as cut off between circles or phases in experience, cut off or winding moved for the pull of power in running, winding moved for hit in transportation, could change the reference of the transformer ,of which the frequency response will be changed, we could detect the deformation according to the frequency response curve.

  • Our company has designed the winding deformation tester base on the idea and the advanced technique.  It could draw the frequency response curve accurately. Then we compare the curves horizontally or vertically to detect the deformation of the transformer.

  • The tester is conformed to the standard of DL/T911 2004.   

  •  

    Sweep Frequency Response Analysis (SFRA) is a powerful and sensitive method[according to whom?] to evaluate the mechanical integrity of core, windings and clamping structures within power transformers by measuring their electrical transfer functions over a wide frequency range. SFRA is a proven method for frequency measurements.

     

     

    Technique Characteristics

     

    1Using the advanced technical of DDS;
    2Using the high speed and advanced microprocessor to design;
    3Using double channels of AD chip of 16 bits;
    4With seven inch LCD touch screen of which the brightness can be adjusted;
    5With thermal printer of which the print thick can be adjusted;
    6It could store one hundred and twenty groups of data, which could be read to current screen or upload to the PC;
    7With PC software using which we could upload data ,test, analyze data, print data, or create word document;
    8Using USB2.0 to connect to the device;
    9Tester dimension:31cm*15cm*5cm;
    10Weight:4.0KG

     

     

     

    Technique Index

     

    1Two different sweep modes: Linear sweep, Section sweep
    Linear sweep0.5KHZ-1MHZinterval 0.5KHZ 2000 dots
    Section sweep50HZ-100HZinterval 2HZ25 dots
    100HZ-1KHZinterval 20HZ45 dots
    1KHZ -10KHZinterval 50HZ180 dots
    10KHZ-100KHZinterval 0.2KHZ 450 dots
    100KHZ – 500KHZ interval 0.5KHZ 800 dots
    500KHZ – 1000KHZ interval 1KHZ500 dots
    2Test range(-100dB) - (+20dB)
    3Test accuracy0.1dB
    4Frequency accuracy<0.01%
    5Signal input impedance>1M Ω
    6Signal output impedance50 Ω