I. Introduction
GDKC-2000 Power Transformer On-load Tap Changer Analyzer is mainly applied to test transient time, transition waveform, transition resistance, synchronization status of three phase.
II. Test Features:
1. Test transformers of type Y0 Y Δ And display resistance value directly;
2. Automatically analyze waveform fault and mark the fault.
3. Automatically adjust resistance value and time range according to sampling data
4. Transformer type Δ Is able to display to synchronization status of three phase;
5. Be able to test with winding or without winding;
6. Four terminal connection mode and provide high accuracy of resistance measurement.
7. Continuous test to save time of power off
8. Make word report
9.800× 480 colorized LCD with touch screen and high speed printer
10. Store 1000 groups of data and also can be saved by USB flash disk
III. Technical Parameters:
1 | Three phase constant current source charge,charge current: 3A/1A; 0.6A/0.2A |
2 | Maximum voltage of the port: 24V |
3 | Maximum range of transition resistance: 100Ω |
4 | Measuring range: 1A : 0.4Ω ~ 20Ω 0.2A : 10Ω ~ 100Ω |
5 | Record time of waveform:300ms |
6 | Sample rate: 30k |
7 | Resolution of time:0.1ms |
8 | Resolution of resistance: 0.1Ω |
9 | Accuracy of transition resistance: ±5% Reading±0.1Ω |
Accuracy of transient time: ±0.5% Reading±0.2mS |
10 | Temperature: -10-40°C Humidity: <85%RH
|