Ⅰ.Introduction

  • GDBC-901 Automatic TTR Transformer Turns Ratio Meter  ( TTR Meter ) is designed according IEC76-1 and IEC60044. 

  • GDBC-901 Automatic TTR Transformer Turns Ratio Meter  ( TTR Meter ) could be applied to test the ratio of single or three phase transformer. Also the connection group of three phase transformer could be calculated with the ratio. All parameters are measured in one test for three phase transformer.

  •  

     

    Ⅱ.Main Functions

     

    1The voltage ratio measurement for three or singe phase transformer
    2The group vector measurement for three phase transformer.
    3The polarity measurement for single phase transformer or CT/PT
    4Voltage ratio error calculation
    5Current transformer ratio measurement
    6Excitation current measurement in ratio testing
    7Reproduction the AC test voltage from power source to reduce the effects of bad power source
    8Save the test results in the memory internal the tester
    9Print the test results by micro printer
    10Reverse connection detect unit to prevent the high voltage injected to operator
    11Over current protection unit integrated in software and hardware
    12Upload the test results to PC by RS232 and make word report by software

     

     

     

    Ⅲ. Technique Index

     

    1Ratio measurement range: 1-10000
    2Group measurement: 1-12
    3Phase measurement error: 1 degree
    4Ratio measurement error: 1-2000 ± 0.2%RDG   2000-10000  ± 0.5%RDG
    5Test voltage:0~80V, frequency 50Hz
    6Power supply: AC220V ± 10%, 50Hz/60Hz
    7Environment temperature: 0-50°C
    8Humidity: ≤85%RH
    9Size 400mm*350mm*200 mm     Weight:7kg

     