Min. Order: | 1 Set/Sets |
---|---|
Trade Term: | FOB,EXW |
Payment Terms: | L/C, T/T, WU |
Supply Ability: | 300 Set/Sets per Month |
Place of Origin: | Zhejiang |
Location: | Wenzhou, Zhejiang, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Model No.: | outdoor VCB |
---|---|
Means of Transport: | Ocean, Air, Land |
VCB: | Vacuum circuit breaker |
circuit breaker: | outdoor VCB |
Production Capacity: | 300 Set/Sets per Month |
Packing: | 1)1 plastic bag/set,1 wooden case/set 2)Special package required by clients |
Delivery Date: | 15-20 days upon receipt of deposit |
ZW7-40.5 outdoor sf6 circuit breaker is with modularized design, anti-interference design, compact structure, free maintenance,
ZW7-40.5 (40.5kV) Vacuum Circuit Breaker, Outdoor Type
1. Prodcut Overview
1.1.Application: for making and breaking load current, overload current and short-circuit protection of electric systems and equipments.
1.2.Standards: IEC 62271-100
1.3.Parameters: Rated voltage up to 40.5kV, Rated current up to 2000A, AC50HZ
Mainly technical parameters | |||
NO | Item | Units | parameters |
1 | Rated voltage | KV | 40.5 |
2 | Rated Frequency | HZ | 50 |
3 | Rated Current | A | 1250 1600 2000 |
4 | Rated short-circuit breaking current | KA | 20 25 31.5 |
5 | Rated short-circuit closing current (peak) | KA | 50 |
6 | Rated short-circuit duration | S | 4 |
7 | Rated short-circuit breaking current breaking number | nos | 30s |
8 | Rated operating sequence | 0-0.3s-CO-180s-CO | |
9 | Rated lightning impulse withstand voltage | kv | 185 |
10 | 1min power frequency withstand voltage | KV | 95 |
11 | Closing time | ms | ≤ 150 |
12 | opening time | ms | ≤ 60 |
13 | Mechanical life | Times | 20000 |
14 | Rated Storage and operation voltage | V | AC DC 220/110 |
15 | Breaking life | ms | ≤ 80 |
16 | Storage life | s | ≤ 10 |
Adjust the parameters of mechanical properties: | |||
No | Item | Unit | Parameters |
1 | Contact distance | mm | 9±1 |
2 | Contact Over-travel | mm | 3±1 |
3 | Closing speed | m/s | 0.6±0.2 |
4 | Opening speed | m/s | 1.5±0.2 |
5 | Contact closing spring time | ms | ≤2 |
6 | Rated contact pressure | N | 20KA(2400±200) |
7 | Three phase closing opening asynchrony | ms | ≤2 |
pepe.eleAToutlook.com