Place of Origin: | Guangdong |
---|
Location: | Beijing, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | CO2 Monitor, CO2 Controller, CO2 Transmitter |
Model No.: | AIA-1 |
---|
Specifications
CO2 Sensor | Non-Dispersive Infrared Detector (NDIR) | |
Measurement Range | 02,000ppm (default) | |
Accuracy | ±60ppm + 3% of reading @22(72) | |
Stability | <2% of full scale over the life of the sensor | |
Calibration | Self-calibration system | |
Response Time | <5 minutes for 90% step change at low duct speed | |
Non-linearity | <1% of full scale @22(72) | |
Duct Air Velocity | 0~450m/min | |
Pressure Dependence | 0.135% of reading per mm Hg | |
Warm up time | 2 hours (first time) | |
Split CO2 sensor | 2 meter cable connection between the senor and the controller | |
Temperature & Humidity Detection&Display (optional) | Temperature | Relative Humidity |
Sensing element: | Band-gap-senor | Capacitive humidity sensor |
Measuring range | -20~60 | 0 -100%RH |
Accuracy | ±0.5 (20~40) | ±4.5%RH (25, 15%-85%RH) |
Display resolution | 0.1 | 0.1%RH |
Stability | ±0.1per year | ±1%RH per year |
General Data |
| |
Power supply | 24VAC/24VDC or 100VAC~240VAC | |
Consumption | 1.8 W max. ; 1.0 W avg. | |
LCD display | Display CO2 measurement | |
Dry contact output (optional) | 1xdry contact output for CO2 | |
Plug& play type | Just for 100VAC~240VAC power supply with European or American power plug and power connector to the CO2 generator | |
Modbus RS485 Interface (optional) | 19200bps, 15KV antistatic protection. | |
Wireless module (optional) | ZigBee 2.4G short distance wireless communication | |
Operation conditions | 0~50(32~122); 0~99%RH, non condensing | |
Storage conditions | 0~60(32~140)/ 0~80%RH | |
IP class | IP30 | |
Standard Approval | CE-Approval |
Features
Typical Applications
Demensions & Mounting
Models Guide
TKG- CO2- A 0 C D Y –TH-PPX
A:the sensor installation type
1: wall mounted with the external adown probe sensor
2: probe duct mounted
3: split sensor with 2 meters cable connection
4: probe duct type with extended probe (209mm)
C:relay dry contact output
0: no dry contact output
1: 1xdry contact output
D:Modbus interface
0: no communication
1: Modbus RS485 interface
2: with ZigBee wireless module (will be provided in the future)
Y:power supply
C: 24VDC/VAC power supply
D: 100~240VAC power supply
-TH temperature & RH detection and display
-PPX Plug and play for wall mounting type
No “PP” indicates without plug & play installation
PPE means European standard plug
PPA means American standard plug
Wiring Diagram