Place of Origin: | Guangdong |
---|
Location: | Beijing, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | CO2 Monitor, CO2 Controller, CO2 Transmitter |
Model No.: | AIA-1 |
---|
Specifications
Power supply |
24 VAC/VDC±20% 50/60HZ |
Electrical rating |
2 Amp load per terminal |
Sensor |
NTC 5K |
Temperature control range |
5-60 (41-95) |
Accuracy |
±0.5 (±1) @25 |
Analog output |
Voltage 1xDC 0V~DC 10V (for F08-LVB-A series) 2 x DC 0V~DC10V (for F08-LVB-A-D series) Current 2 mA |
Relay output |
1 or 2 outputs with 2 Amp load |
Protection class |
IP30 |
Environment condition |
Operating temperature: 0 – 50 Operating humidity: 5 ~99% RH Storage temperature: -10 – 60 0C Storage humidity: < 95%RH |
BACnet interface |
BACnet MS/TP with adjustable baud-rate |
Display |
LCD |
Net Weight |
280g |
Dimensions |
120mm(L)×90mm(W)×24mm(H) |
Housing |
PC/ABS plastic material with IP30 protection class |
Mounting standard |
Mounting on the wall, or 2“×4“/ 65mm×65mm pipe box |
Feartures
1. Typical used in buildings for VAV systems
2. Designed for BACnet MS/TP networks with 1x0~10 VDC output to cooling/heating air damper or 2x0~10VDC outputs to cooling and heating air dampers, also with one or two relay outputs to one or two stages electric auxiliary heater
3. A PIC statement is supplied to be easily mapped back to a graphical user interface.
4. Self configuring / adjustable baud-rate senses the communication conditions of the current MS/TP network and match them.
5. BACnet PIC statement provided to further facilitate integration.
6. LCD can display working status such as room temperature, set point, analog output, etc. Makes reading and operating easy and accurate.
7. Up to two-stage electric aux. heater control makes temperature controlling more accurate and energy-saving.
8. Large set point adjustment, the mini. and max. limit of temperature preset by end users
9. Celsius or Fahrenheit degree selectable
10. Cooling/heating mode auto changeover or manual switch selectable
11. Two parts structure and quick wire terminal blocks make mounting easily.
12. Infrared Remote Control (optional)
Models
Type |
Model |
Characteristic |
|
Bacnet Room Thermostat for VAV Systems
Power supply: 24VAC/VDC |
F08-LVB-N-(C) |
1X 0~10V output for an actuator of VAV terminal with cooling/heating switch |
|
F08-LVB-A01-(C) |
1X 0~10V output for an actuator, 1X on/off contact output to a heater. Cooling/heating switch. |
||
F08-LVB-A02-(C) |
1X 0~10V output for an actuator, 2X on/off contact outputs for 2-stage heater. Cooling/heating switch |
||
F08-LVB-D-(C) |
2X 0~10V outputs for cooling and heating |
||
F08-LVB-D01-(C) |
2X 0~10V outputs for cooling and heating, 1xon/off contact output for an aux. heater |
||
OPTIONS |
|||
Accessional Options |
Backlight -EL |
LCD blue backlight |
|
Remote Control -R |
Infrared remote control |
|
Button and LCD
Dimension & Mounting
Wiring Diagram