Place of Origin: | Guangdong |
---|
Location: | Beijing, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | CO2 Monitor, CO2 Controller, CO2 Transmitter |
Model No.: | AIA-1 |
---|
Specifications:
Carbon Dioxide |
|||
Sensing element |
Non-Dispersive Infrared Detector (NDIR) |
||
CO2 measuring range |
0~2000ppm/ 05,000ppm optional |
||
CO2 Accuracy @22(72) |
±40ppm + 3% of reading or ±75ppm (whichever is greater) |
||
Temperature dependence |
0.2% FS per |
||
Stability |
<2% of FS over life of sensor (15 year typical) |
||
Pressure dependence |
0.13% of reading per mm Hg |
||
Calibration |
ABC Logic Self Calibration Algorithm |
||
Response time |
<2 minutes for 90% step change typical |
||
Signal update |
Every 2 seconds |
||
Warm-up time |
2 hours (first time) / 2 minutes (operation) |
||
|
Temperature |
Humidity |
|
Measuring range |
0~50(32~122) (default) |
0 ~100%RH |
|
Accuracy |
±0.4 (20~40) |
±3%RH (20%-80%RH) |
|
Display resolution |
0.1 |
0.1%RH |
|
Stability |
<0.04/year |
<0.5%RH/year |
|
General Data |
|||
Power supply |
24VAC/VDC |
||
Consumption |
1.8 W max. ; 1.2 W avg. |
||
Analog outputs |
1~3 X analog outputs 0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at placing the order) |
||
Modbus communication (optional) |
RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address. |
||
Operation conditions |
0~50(32~122); 0~95%RH, non condensing |
||
Storage conditions |
10~50(50~122), 20~60%RH non condensing |
||
Net Weight |
240g |
||
Dimensions |
130mm(H)×85mm(W)×36.5mm(D) |
||
Installation |
wall mounting with 65mm×65mm or 2”×4”wire box |
||
Housing and IP class |
PC/ABS fireproof plastic material, protection class: IP30 |
||
Standard |
CE-Approval |
Description:
Applications:
Mounting and Dimension:
Models Guide:
G01-CO2-B X 0 C –Y 0 Z –U 02/05 –T/TH –Txx
X: LCD or no LCD
1- Without LCD, 24VAC/VDC power supply
3- LCD display, 24VAC/VDC power supply
C: 24VAC/VDC power supply
Y: analog output quantity
3-3Xanalog outputs (for CO2, temperature, humidity)
2-2Xanalog outputs (for CO2, temperature)
1-<