user login

Carbon Monoxide And Gas Detector For Underground

Place of Origin: Guangdong

Company Profile

Location: Beijing, China (Mainland)
Business Type: Manufacturer
Main Products: CO2 Monitor, CO2 Controller, CO2 Transmitter

Product Detail

Model No.: AIA-1

Product Description

Specifications
 

Sensors

Gas Sensor

Electrochemical carbon monoxide sensor

Sensor lifetime

Typically more than 3 years, replaceable

Warm up time

60 minutes (for the first time use)   

Response Time

Within 60 seconds

Signal Update

1s

CO Measuring Range

0~100ppm(default)/0~200ppm/0~500ppm  selectable

Accuracy

<1ppm+5%reading

Stability

±5% (over 900 days)

 

Temperature & Humidity Sensor (optional)

Temperature

Relative Humidity

Sensing element:

Band-gap-senor

Capacitive humidity sensor

Measuring range

-10~60

0 -100%RH

Accuracy

±0.5 (20~40)

±4.0%RH (25, 15%-85%RH)

Display resolution

0.1

0.1%RH

Stability

±0.1 per year

±1%RH per year

 

Outputs

LCD Display (optional)

Display real time CO measurement
or CO+ temperature& humidity measurements

Analog Output

1X010VDC or 4~20mA linear output for CO measurement

Analog Output Resolution

16Bit

Relay dry contact Output

Up to two dry-contact outputs
Max, switching current 3A (230VAC/30VDC), resistance Load

RS485 communication interface

Optional Modbus RTU protocol with 19200bps(default),
Or BACnet MS/TP protocol with 38400bps(default)

 

Electrical and General Items

Power Supply

24VAC/VDC                

Power Consumption

2.8W

Wiring Standard

Wire section area<1.5mm2

Working Condition

-10~60(14~140); 5~99%RH, non condensing

Storage Conditions

-10~60(14~140)/ 5~99%RH, non condensing

Net Weight

260g    

Manufacturing Process

ISO 9001 Certified

Housing and IP class

PC/ABS fireproof plastic material, protection class: IP30

Compliance

CE-EMC Approval


 
Description
 
1. Design for real-time detection air carbon monoxide.
2. High accuracy humidity and temperature detection optional
3. LCD display carbon monoxide and optional temperature & RH measurement.
4. Smart buttons for easy operation
5. Excellent electrochemical CO sensor with more than 5 years life time
6. Replaceable CO sensor
7. Provide 1X analog linear output (0~10VDC/4~20mA selectable) for the measurement
8. Providing up to two dry contact outputs with presetting the setpoint
9. Modbus RS485 communication interface optional
10. Provide two easy methods for calibration and setup alarm points by end users: infrared remote controller or a software via RS485
11. 24VAC/VDC power supply
12. CE-Approval
 
Applications
 
a. In office and residence areas to detect CO level
b. In underground parking lots and garages
c. In BAS to detect the CO and the data transmittance 
d. For greenhouse and plant bin
e. For ventilation control system
 
Mounting and Dimensions
 
 
 
 
Wiring Diagram
 
 
 
Models Guide
 
TKG- CO- 1 X Y Z C - TH-R
 
1:  wall mounted with the external sensor in an adown probe
 
X: analog output
          0: no analog output
          1: 1x0~10VDC linear output(default)
          2: 1X4~20mA linear output (default)
          3: 1X0~10VDC output and can be switch to 4~20mA (just for only one analog output)
          4: 1x0~5VDC linear output (default)
 
Y: relay dry contact output
         0: no dry contact output
1: 1xdry contact output
2: 2xdry contact outputs
 
Z: communication interface
         0: no communication
         1: Modbus RS485 interface
         9: Bacnet MS/TP interface
 
C: 24VDC/VAC power supply
 
-NL(option)  No LCD display, only for the transmitter which only has one analog linear output. 
 
-TH(option)  temperature & RH detection and display
No –TH indicates without temperature & RH detection and display
 
R: CO range
     005: 0~500ppm (default)
     001: 0~100ppm
     002: 0~200ppm
 
For example: TKG-CO-1101C-TH-001 indicates the CO detector with 1X0~10VDC linear output and Modbus interface. CO range:0~100ppm. It has temperature and humidity detection and display.
 
 