user login

China Supplier of Frequency Tuned Resonant Test Set

1000.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB,CFR,CIF,EXW
Payment Terms: L/C, T/T
Supply Ability: 50 sets per year
Place of Origin: Hubei

Company Profile

Location: Wuhan, Hubei, China (Mainland)
Business Type: Manufacturer, Trading Company
Main Products: Resonant Test System, Dielectric Strength Test Set

Product Detail

Model No.: SXBP
Means of Transport: Ocean, Air, Land
Production Capacity: 50 sets per year
Packing: Plywood cases
Delivery Date: 10-30 working days
Show

Product Description

AC resonant test system is used for factory testing of middle, high and ultra-high voltage cables, capacitors, generators, motors, power transformers and gas-insulated switchgears.

The resonant test systems can be either in insulation cylinder type or metal tank. Insulation cylinder reactors are in module and can be stacked to connect in series parallel to get much higher voltage or current. Additional voltage taps are possible for metal tank reactors. The output voltage is fed out through the tap-changers by HV bushings. This kind of reactors extend application range, and satisfy testing for cables of various voltage class.


SXBP-528kVA/440kV Variable Frequency AC Series Resonant Test System 
The system is consisted by below units:  
√ Variable Frequency Power Generator
√ HV Divider
√ Exciting Transformer
√ HV Reactor
√ Compensation Capacitor (optional)
√ Accessories Box (connection wires)

Ex-work Testing
Packing


Test Object and Requirement
The system is specially designed for AC withstand voltage test for below items, with below specifications and requirements.    
AC withstand voltage test for 80MVA/220kV.
AC withstand voltage for 103MW generator, test voltage 22.95kV. 
AC withstand voltage for 203KV GIS, max. test voltage 440kV.

 Technical Data 
√  Rated capacity: 528kVA
√  Input power supply: three phase 380V, 50Hz
√  Rated voltage: 40kV/200kV/440kV
√  Rated current: 12A/2.4A/1.2A
√  Working Frequency: 30-300Hz
√  Output waveform: sine wave
√  Waveform distortion rate: ≤1%
√  Working time: Constant working of 60mins under rated load. Working of 1min, under 1.1 times of rated voltage
√  Temperature rise: ≤65K after constant working of 60mins under rated load
√  Quality factor: Q ≥30 (f=45Hz)
√  Protective function: Over-current, over-voltage and flashover protections for test object.
√  Accuracy: 1.5% (RMS)

 


More information, please kindly contact with us, we can customize the suitable test set according your requirements and give you the best quotation. Thank you! 


Post Buying Request