VS1 Indoor Electrical Vacuum Circuit Breaker 630Amp Fix Type GB198489
Benefits:
1. Modular spring operating mechanism, easy installation and maintenance
2. New vacuum interrupter of high vacuum and ultra-low resistance,stronger breaking capacity,insulation recover faster, lower contact resistance
3. Item models fully cover the rated current from 630A to 4000A and the rated breaking current from 20kA to 50kA
4. Two installation type: stationary-type, handcart-type
5. With wrong operation prevention interlock,keep risks away
6. Easy control and low maintenance
Application:
Industry factory
Mining enterprise
Power plant
Substation
and etc.
serving condition:
1.Ambient temperature: ≤+40 °C and ≥ -10°C (storage and transportation is allowed at -30 °C minimum).
2. Altitude: ≤1000m.
3. Humidity: daily average ≤ 95%, monthly average ≤ 90%
4. Saturated vapor pressure: daily average≤2.2 kPa, monthly average≤1.8 kPa.
5. Earthquake intensity: ≤8.
6. No applicable for the place: fire, explosion hazard, pollution class above 2, chemical corrosion, intense vibration.
Specification:
No. | Item | Unit | Data | ||
1 | Rated voltage | kV | 12 | ||
2 | Rated frequency | Hz | 50 | ||
3 | Rated lightning impulse withstand voltage (peak) | kV | 75 | ||
4 | Rated power frequency withstand voltage (1 min) | kV | 42 | ||
5 | Rated short sircuit breaking current | kA | 20 | ||
6 | Rated current | A | 630 | ||
1250 | |||||
7 | Rated short time withstand current (virtual value) | kA | 20 | ||
8 | Rated peak withstand current (peak) | kA | 50 | ||
9 | Rated short-circuit making current (peak) | kA | 50 | ||
10 | Rated short-circuit current duration | s | 4 | ||
11 | breaking time of short-circuit current | times | 50 | ||
12 | Mechanism life | times | 2000 | ||
13 | Secondary circuit power frequency withstand voltage (1 min) | V | 2000 | ||
14 | Rated operation order | O-0.3S-CO-180S-CO | |||
15 | Rated single/back-to-back capacitor bank breaking current | A | 630/400 | ||
16 | Rated capacitor bank making current | KA | 12.5(frequency≤1000HZ) | ||
17 | Contact distance | mm | 11±0.1 | ||
18 | Contact over travel | mm | 3.5±0.5 | ||
19 | Contact closing tripping time | ms | ≤2 | ||
20 | Three-phase breaking /closing non-synchronism | ms | ≤2 | ||
21 | Average switch-off speed | m/s | 1±0.2 | ||
22 | Average switch-on speed | m/s | 0.6 +0.2 | ||
-0.1 | |||||
23 | Switch-off (rated voltage) | ms | 20~60 | ||
24 | Switch-on (rated voltage0 | ms | 30~70 | ||
25 | Rated operation voltage | V | AC110/220,DC110/220 | ||
26 | Rated voltage of charging motor | V | AC110/220,DC110/220 | ||
27 |
|