High Power Density 150Ah 12v 10Hr VRLA UPS battery CE UL Certification

Place of Origin: Zhejiang

Company Profile

Location: Dongguan, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: VRLA GEL Battery, VRLA Deep Cycle Battery, VRLA UPS Battery

Product Detail

Model No.: JP12-200

Product Description

High Power Density 150Ah 12v 10Hr VRLA UPS battery CE UL Certification

 

Jopower JP series SLA AGM batteries are designed for general-purpose applications, such as UPS, telecom, and electrical utilities.

 

With 5 years design life, the batteries comply to the most popular international standards, such as IEC60896-21/22, BS6290-4, Eurobat Guide. The battery container and cover are available both in V0 class flame retardant ABS or HBO ABS plastics. With more than 15 years of production experience, JP series of VRLA AGM batteries are recognized as the most reliable and high quality battery system in the industry. Product Standards You can expect our batteries meet with the standards JIS, DIN, IEC60986-21/22 & BS6290-4. We have obtained ISO9001 & ISO14001 certification.

 

We have obtained UL approval for all types of batteries. We have obtained CE approval for all types of batteries. All these render our batteries to be compatible with requirements of world-level equipments.

 

General Features:

• Environmentally friendly

• High Reliability and Good Quality

• Lower internal Resistance

• High Power Density

• Long Service Life, in Float and Cyclic

• International Standard, JIS and DIN

• lead-tin-calcium alloy grids for long service life

 

Applications:

• UPS • Telecom Systems • Solar Systems • Cable TV

• Electric Wheelchair • Power Station • Marine Equipment

• Military Equipment • Golf Car • Electric Fork

• Emergency Power System • Railway System

 

 
Battery Model JP12-200
Designed Floating life 5 years
Dimensions(mm) Length Width Height Total height
  522 240 218 223
Approx Weight 59.00kg
Internal Resistance Full charged at 20: 0.0030Ω
Self Discharge <3% per month at 20 
Capacity Affected by Temp.(10Hr) 40  20  (-15)
  109% 100% 85% 65%
Charge Voltage (20 ) Cycle use Float use
  14.4-14.8v max current: 50A 13.6-13.8v
 

 

 