Large-screen LCD
Model # | CE2K | CE2KS | Comments | |
Input voltage | ||||
Rated voltage | 220VAC | |||
Phase | Single phase with ground | |||
Turn on voltage range | (90±5285±5)VAC | |||
Bypass voltage range | 80VAC~286VAC(default:80VAC~264VAC) | Could be adjusted by software. | ||
Bypass low loss | 80VAC~220VAC(default:80VAC) | |||
Bypass low comeback | Low loss+10VAC | |||
Bypass high loss | 220VAC~286VAC(default:264VAC) | |||
Bypass high comeback | High loss -10VAC | |||
Line low loss/comeback | (90±5) VAC /(110±5) VAC | load≤30 | PF0.7 | |
(110±5)VAC/(125±5)VAC | 30load≤60 | |||
(120±5) VAC /(135±5) VAC | 60load≤70 | |||
(140±5) VAC /(155±5) VAC | 70load≤80 | |||
(160±5) VAC /(170±5) VAC | load80 | |||
(90±5) VAC /(110±5) VAC | load≤30 | PF0.8 | ||
(110±5) VAC /(125±5) VAC | 30load≤55 | |||
(130±5) VAC /(145±5) VAC | 56load≤65 | |||
(150±5) VAC /(165±5) VAC | 66load≤70 | |||
(160±5) VAC /(175±5) VAC | load70 | |||
Line high loss/comeback | (300±5)VAC/(285±5)VAC | 0≤load100 | ||
Input frequency | ||||
Rated frequency | 50Hz | |||
Frequency low loss | (40~49)±0.2Hz(default:46Hz) | Could be adjusted by software. | ||
Frequency low comeback | Frequency low loss + 0.5Hz | |||
Frequency high loss | (51~60)±0.2Hz(default:54Hz) | |||
Frequency high comeback | Frequency high loss - 0.5Hz | |||
Input power factor | ||||
Input power factor | 0.99 | 220VAC,full R load | ||
Generator | Support generator input | Generator rating≥2*UPS rating | ||
Input current | ||||
Rated current | 9.1A | 220VAC,full RCD load | ||
Input THDI | ≤10% | 220VAC,full RCD load,The mains THDI≤4% | ||
Output protection | ||||
Rating protection | 20A AC fuse | |||
Output power | ||||
VA/watt | 2000VA/1400W~1600W | Could be adjusted by software. | ||
Rated voltage | 220VAC | Pure Sine wave | ||
Voltage range | 200VAC/208VAC/220VAC/230VAC/240VAC | Could be adjusted by software. 10% derating for 208VAC/200VAC. | ||
Voltage regulation | ±2 | |||
Voltage distortion | ≤7 | Full RCD load | 220VAC;battery full charged | |
≤4 | Full R load | |||
DC offset | ≤±200mV | |||
Transient response | ≤9 | R load 01000 | ||
≤6 | R load 2010020 | |||
Transient recovery | ≤60ms voltage recovery to 90% | Full RCD load | ||
Bypass output before turn-on | Default:No | Could be set by software. | ||
Crest ration | 3:01 | |||
Output frequency range | ||||
Normal mode | 1,Same as input frequency(46Hz~54Hz) | |||
2,50Hz(Input frequency>54Hz or Input frequency<46Hz) | ||||
Battery mode |
|