50HZ / 60Hz 220V / 380V High Frequency Online UPS Commercial Ups Systems

Place of Origin: Zhejiang

Company Profile

Location: Shenzhen, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: Low Frequency Online UPS, High Frequency Online UPS, Rack Mount UPS

Product Detail

Model No.: CE10KS , CE15KS , CE20KS

Product Description

 

10-20Kva Three Phase Input Single Phase Output High Frequency Online UPS 380V / 220Vac

 

DSP Technology

Active input power factor correction (PFC)

Wide range of input voltage and frequency

Zero power switch delay

Active Load Management

Sufficient Expansion Slots

The load power factor is 0.8

Support the Generators: The wide range of input voltage and frequency can effectively separate the harmful electric wave produces by the generators and provide safe and reliable power supply.

 

 

Model# 3CE10K 3CE15K 3CE20K Comments
Input
Input voltage
Rated voltage 380VAC/220VAC
Phase three phase with ground
Turn on voltage range (120±5274±5)VAC
Bypass voltage range (60±5300±5)VAC Could be adjusted by software.
Bypass low loss 60VAC~220VAC(default 60VAC)
Bypass low comeback Low loss +5VAC
Bypass high loss 220VAC~300VAC(default 300VAC)
Bypass high comeback High loss -5VAC
Line low loss/comeback (120±5) VAC /(140±5) VAC load≤50
(150±5) VAC /(165±5) VAC 50load≤80
(160±5) VAC /(180±5) VAC load80
Line high loss/comeback (274±5)VAC/(260±5)VAC
Input frequency
Rated frequency 50Hz
Frequency low loss (40~49) ±0.2Hz(default:46Hz) Could be adjusted by software.
Frequency low comeback Frequency low loss +0.5Hz
Frequency high loss (51~60)±0.2Hz(default:54Hz)
Frequency high comeback Frequency high loss -0.5Hz
Input power factor
Input power factor > 0.95 220VAC,full R load
Generator  Support generator input Generator rating≥2*UPS rating
Input current
Rated current  45A 68A 91A
Input THDI <= 25%
Output protection
Rating protection 50A Breaker 80A Breaker 100A Breaker
Output power
VA/watt 10KVA/8KW 15KVA/12KW 20KVA/16KW
Rated voltage 220VAC Sine wave
Voltage range 200/208/220/230/240VAC Could be adjusted by software. 10% derating for 208VAC/200VAC.
Voltage regulation ±1%
Voltage distortion ≤6 Full RCD load
≤2 Full R load
DC offset ≤200mV
Transient response ≤9 R load 01000
≤6 R load 2010020
Transient recovery ≤60ms voltage recovery to 90% Full RCD load
Bypass output before turn-on YES
Crest ration 3:01
Output frequency range
Normal mode 1,Same as input frequency(46Hz~54Hz)
2,50Hz(Input frequency>54Hz or
Input frequency<46Hz)
Battery mode (50+0.1) Hz
Slew rate 1 Hz/Sec
Efficiency
Normal  mode > 90%
Battery mode > 88%
Overload
 Normal mode/battery mode  Overload warning only 105%±5%≤load
1min,then transfer to bypass and alarm. 105%±5%<load≤125%±5%
30S,then transfer to bypass and alarm. 125%±5%<load≤135%±5%
100mS, then transfer to bypass and alarm.  load>135%±5%
Automatically retransfer YES