Model No.: HP9117CR Series 1 - 3KVA

Product Description

High Frequency Uninterrupted Power Supply UPS Rack Mountable For network 

 

 

Key Features:
Protects against downtime, data loss and process interruption by providing continuous, clean power
Offers premium performance with a 0.9 power factor and >95% efficiency
Increases battery service life and system uptime with ABM battery charging technology
Enables prolonged runtime of essential equipment during power outages by allowing for orderly, remote shutdown of non-critical systems or processes thanks to a capability to control load segments.
Provides installation flexibility with a choice of rack or tower designs, both conserving valuable space
Can replace batteries online, convenient for user to use
Enhanced monitoring and configuration capability through easily navigated multilingual graphical display.

Replace battery online:               ABM Technology:
 

Application :
IT and network environment, servers and network devices, telecom, VoIP and security systems, medical systems, diagnosis and medical screening system, Patient record archives, Manufacturing systems, Chip fabrication, Pharmaceutical production, Chemical processing

Technical Specifications of Rack mount UPS HP9117C Series

Model

HP9117CR 1-3KVA

1KR

1KR-XL

2KR

2KR-XL

3KR

3KR-XL

Capacity

1KVA/900 W

2KVA/1800 W

3KVA/2700 W

Nominal Voltage

100/110/120/127VAC or 200/208/220/230/240VAC

Nominal Frequency

50/60 Hz

Input

Voltage Range

60-138VAC or 115-276VAC

Frequency Range

50HZ:(4654HZ)60HZ:(56HZ64HZ)

Power Factor

0.98

Output

Voltage precision

100/110/120/127VAC(±2%) or 200/208/220/230/240VAC (±2%)

Frequency precision

50Hz/60Hz±0.05Hz

Power Factor

0.9

Harmonic Distortion

Linear Load3%    Non-Linear Load5%

Overload capacity

overload(110%150%)after 30 seconds automatically transfer to bypass, it recover after  normal load

Current Crest Ratio

31

Transfer time

0ms(AC→DC)

Battery

DC voltage

36VDC

96VDC

96VDC

Recharge time

7 hours to 90%

Charge Current

1A

4A/8A(option)

1A

4A/8A(opt