Place of Origin: | Zhejiang |
---|
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | NDT Instruments, Environmental Testing Equipment |
Model No.: | LXC7220 |
---|
Automatic voltage regulator AS480 avr for alternator generator, Operating Temperature -40 to +70 Deg. C
Description-
SPECIFICAON
The AS480 is a half-wave phase-controlled AVR which forms part of the excitation structure of the brushless generator.
Which also incorporates
an interface to the optional excitation boost system(EBS) for the use where short-circuit current safeguarding is required.
Positive voltage build up from residual levels is ensured by the use of proficient semiconductors in the power circuitry of the
AVR. The control and voltage sensing circuits have separate terminals,
allowing the excitation power to be resulting directly from the stator winding for necessary applications or from an auxiliary
winding if sustained short circuit performance is essential. Which is linked with the main stator windings and the exciter field
windings to offer closed loop control of the output voltage with load regulations of +/- 1.0%, In response to his sample voltage, the AVR controls the power fed to the exciter field, and hence the main
field, to sustain the machine output voltage within the specified limits, compensating for load, speed, temperature and power factor of the generator.
Sensing Input | Voltage | 100-264 V ac 1 phase | ||
Frequency | 50-60 Hz nominal | |||
Output | Voltage | 82 V d.c. @ 200 Va.c power input; 45 V d.c. @ 110 Va.c power input. | ||
Current | Continuous 5A , transient 7.5A for 10 secs. | |||
Resistance | 15 ohms minimum | |||
Regulation | +/- 1% | |||
Thermal Drift | 0.03% per Deg. C change in AVR ambient | |||
Typical system Response |
AVR response | 20ms | ||
Filed current to 90% |
80 ms | |||
Machine Volts to 97% |
300ms | |||
External voltage adjustment | +/-10% with 1 k ohm 1 watt trimmer; Increasing resistance lowers voltage; Fixed 15kOhm resistor enables 110V sensing | |||
Under frequency protection | Set point: 94 -98% Hz | |||
Unit power dissipation | 12 watts maximum | |||
Build up voltage | 4 Volts @ AVR terminals | |||
QUADRATURE DROOP INPUT | 10 ohms burden | |||
Max. sensitivity: 0.07 A for 5% droop 0PF | ||||
Max. input: 0.33 A | ||||
Over Excitation Protection |
Set poit | 67 Vdc +/-3% (fixed | ||
Time Delay | 10-15 seconds (fixed) | |||
Environmental | Vibration | 20-100 Hz,50mm/se | ||
100Hz – 2kHz, 3.3g | ||||
Operating Temperature |
-40 to +70 Deg. C | |||
Relative Humidity 0-70 Deg. C |
95% | |||
Storage Temperature |
-55 to +80 Deg. C |
Edited by Lisa Sun