Place of Origin: | Zhejiang |
---|
Location: | Dongguan, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Air Cooled Modular Chiller, Air Cooled Screw Chiller, Air Handling Units |
Model No.: | EKDC |
---|
High Efficiency Water-cooled Falling Film Centrifugal Chiller
Specification
Model | EKDC1200 | EKDC1300 | EKDC1400 | EKDC1500 | ||
Nominal Cooling | Cooling Capacity | U.S.RT | 1223 | 1325 | 1427 | 1529 |
kW | 4302 | 4661 | 5019 | 5378 | ||
x104kCal/h | 370 | 401 | 432 | 463 | ||
Input Power | kW | 698 | 760 | 822 | 879 | |
COP | kW / kW | 6.16 | 6.13 | 6.11 | 6.12 | |
Chilled Water Flow | m3/h | 740 | 802 | 863 | 925 | |
Chilled Water Pressure Drop | kPa | 95 | 95 | 96 | 98 | |
Cooling Water Flow | m3/h | 860 | 932 | 1005 | 1076 | |
Cooling Water Pressure Drop | kPa | 97 | 98 | 98 | 98 | |
Cooling* | Cooling Capacity | U.S.RT | 1194 | 1293 | 1393 | 1492 |
kW | 4199 | 4549 | 4899 | 5249 | ||
x104kCal/h | 361 | 391 | 421 | 451 | ||
Input Power | kW | 721 | 785 | 849 | 908 | |
COP | kW / kW | 5.82 | 5.79 | 5.77 | 5.78 | |
Chilled Water Flow | m3/h | 722 | 782 | 843 | 903 | |
Chilled Water Pressure Drop | kPa | 90 | 90 | 92 | 93 | |
Cooling Water Flow | m3/h | 846 | 917 | 989 | 1059 | |
Cooling Water Pressure Drop | kPa | 94 | 95 | 95 | 95 | |
Compressor | Type | Two Stage Semi-hermetic Centrifugal | ||||
Start Type | Directly(High Voltage) | |||||
Power Supply | 6kV/3Ph/50Hz, 10kV/3Ph/50Hz | |||||
Condenser | Type | Shell-Tube | ||||
Qty. | 1 | 1 | 1 | 1 | ||
Evaporator | Type | Spray ( Falling Film) | ||||
Qty. | 1 | 1 | 1 | 1 | ||
Refrigerant | R134a | |||||
Control Type |
You Might Also Like |