user login

China Made CT PT Analyser Tester

6.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB,CFR,CIF,EXW
Payment Terms: L/C, T/T
Supply Ability: 300 sets per month
Place of Origin: Chongqing

Company Profile

Location: Chongqing, China (Mainland)
Business Type: Manufacturer
Main Products: Electric Tester , Oil Purifier

Product Detail

Model No.: GDVA-405
Means of Transport: Air
Production Capacity: 300 sets per month
Packing: standard wooden case and carton
Delivery Date: 15 working days after receving deposit
Show

Product Description

1.1 Application

Tests for Current Transformer:

1)Excitation curve and parameters test

2)Turns ratio test

3)Ratio and phase error test

4)Polarity mark check

5)Winding resistance measurement

6)Secondary loop burden measurement

7)Error line curve test for protection CT

8)Transient CT parameters test

9)CT nameplate guess

10) Saturation hysteresis loop curve measurement

 

Tests for Voltage Transformer:

1) Turns ratio test

2) Ratio error and phase angle error test

3) Polarity test

4) Secondary burden test

5) Winding resistance test

 

Applications of CT PT Analyser  :

1) CT nameplate check

2) CT parameters check in work burden

3) CT transient parameters analysis

4) CT ratio and phase error calibration

5) PT routine test

1.2   CT PT Analyser and Technical Index

1) Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13

2) Power supply: AC220V±10%, 50/60Hz±10%

3) Voltage output: 0.1~180V (AC)

4) Current output: 0.001~5A(RMS)

5) Power output: 500VA

6) Maximum knee voltage measurement: 45KV

7) Current measurement:

Range: 0~10A (automatically change range in 0.1/0.4/2/10A)

Error: <±0.1%+0.01%FS

8) Voltage measurement:

Range: 0~200V (automatically change range in 1V/10V/70V/200V)

Error: < ±0.1%+0.01%FS

9) Turns ratio measurement:

Range:1~35000

1~2000     error<0.05%

2000~5000  error<0.1%

5000~35000  error<0.2%

10) Phase measurement: error: ±2min; resolution: 0.01min

11) Winding resistance measurement: 

Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)

Error: < 0.2%RDG+0.02%FS

Maximum resolution: 0.1mΩ

12) Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree

13) CT Secondary burden:

Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

Error: <0.2%RDG+0.02%FS 

Maximum resolution: 0.001ohm

14) PT Secondary burden:

Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)

Error :<0.2%RDG+0.02%FS 

Maximum resolution: 0.1ohm

15) PT ratio measurement:

Range: 1~35000

1~10000 error<0.1%

10000~35000 error<0.2%

16) PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%

17) PT phase angle measurement: maximum error < 3min

18)Make evaluation for test results according to selected standards

19) Make word report for test result

20) Make word reports one time for multi-group test records on the PC

21) Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test

22) Compare excitation curves with saved excitation curves in the same window

23) Memory capacity: >1000 groups test results 

24)Working condition: temperature: -10℃~50℃; moist: ≤90%

25) Size: 485mm×356mm×183mm

26) Weight: <15kg 


Post Buying Request