Min. Order: | 1 Set/Sets |
---|---|
Trade Term: | FOB,CFR,CIF,EXW |
Payment Terms: | L/C, T/T, WU |
Supply Ability: | 300 sets per month |
Place of Origin: | Chongqing |
Location: | Chongqing, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Electric Tester , Oil Purifier |
Model No.: | GDJB-III |
---|---|
Means of Transport: | Air |
Production Capacity: | 300 sets per month |
Packing: | Standard wooden case |
Delivery Date: | 15 working days once order comfirm |
1. General introduction:
GDJB-III Single Phase Secondary Injection Relay Test System is used to adjust and test relaying protection tester of power supply system. It's high precision, full function, stable performance, easy operation and so on.
2. Functions:
DC voltage relay test;
DC current relay test;
AC voltage relay test;
AC current relay test;
High current injection;
Time counter in relay test;
3. Technique index:
1. DC voltage output:0~350V continuous adjustable, output capacity:960VA
2. AC voltage output:0~380V continuous adjustable, output capacity:400VA
3. DC current output:0~10A continuous adjustable, output capacity:80VA
4. AC current output:0~10A 0~100A,capacity:1000VA
5. Volt ampere feature test: voltage 0~240V current 0~5A
6. AC short circuit voltage analog output
7. DC voltage selection output(it can be used as the operation power of static relay)Output Voltage:24V,48V,110V,220V,all the output current is 0.4A
8. Device precision:0.5 grade
9. Joint action time test:0~9999s
10. Resolution:1ms.
11. Power supply: AC220V+/-10%, 50Hz/60Hz;
12.Environment temperature: 0-50 centigrade;
13.Size:550mm*410mm*340mm
14.Weight:33kg