user login

LCD Display H.V Circuit Breaker Tester

6.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB
Payment Terms: L/C, T/T, Cash, WU
Supply Ability: 300 sets per month
Place of Origin: Chongqing

Company Profile

Location: Chongqing, China (Mainland)
Business Type: Manufacturer
Main Products: Electric Tester , Oil Purifier

Product Detail

Model No.: GDGK-306
Means of Transport: Air
Function: H.V Circuit Breaker Tester
Test Objects: indoors/outdoors switches,vacuum switches etc
Production Capacity: 300 sets per month
Packing: Standard wooden case
Delivery Date: 15 working days once order comfirm
Show

Product Description

1.1 General introduction

GDGK-306  H.V Circuit Breaker Tester is special instrument for power system GIS mechanical properties measuring.

GDGK-306  H.V Circuit Breaker Tester takes ARM7 for the core to process the test data. With high intelligence, lots of functions, accurate test data, strong anti-jamming, easy operation, small size, light weight and so on,

GDGK-306  H.V Circuit Breaker Tester is applicable to all kinds of GIS mechanical properties measuring such as indoors or outdoors switches with less oil or more oil, vacuum switches, sulfur hexafluoride switches and so on.

 

1.2 Major testing items and functions

1  Measure opening time and closing time of 12 interfaces of GIS

2  Measure opening time and closing time of continuous on and off of GIS

3  Test the synchronization performance  

4  Measure bounce time and bounce times of vacuum switches

5  Measure the distance from GIS off to the point on which the two contacts touch each other instantly.

6  Measure the distance from the point on which the two contacts touch each other instant to the point on which two contacts stop moving.

7  Measure speed at instant of GIS on and GIS off.

8  Measure the maximum speed of GIS on and GIS off

9  Measure the average speed of GIS on and GIS off

10 Display and print the speed-time curve, the distance-time curve ,the speed-distance curve and the current-time curve.

 

1.3Technique index

1) Time measuring:

Number of interface of GIS measured :≤12

Range of the setting time during the measuring course: 0 to 6 seconds

Resolution: 0.01ms

2) Distance measuring:

Range: <250mm

Resolution: 0.01mm

3) Errors of measuring

Error of time measuring: ±1%

Error of distance measuring: ±1mm

4) Speed measurement range: 0—20m/s

5) Power output

Output voltage: 20V—220V  error: 1%

Output current: 0~20A

6) Operating conditions

Rated power supply: AC220V±10%, 50HZ

Power consumption: ≤60W

Temperature of environment: 0~40°C

Humidity of environment: ≤90%RH

Size: 400mm*350mm*200mm

Weight: 7kg


Post Buying Request