Place of Origin: | Zhejiang |
---|
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Uninterrupted Power Supply, Offline UPS, High Frequency Online UPS |
Model No.: | Green Star Series 1-20Kva |
---|
Pure Sine Wave 6 Kva / 10 Kva / 15Kva / 20Kva Double Conversion Online UPS with both 220Vac and 380Vac Input
Model:High Frequency Online UPS Green Star Series 6K-20Kva (1ph in / 1ph out) (3ph in / 1ph out)
Quick Read
1: UPS with EMI/RFI noise filter .
2: Smart communication ports of RJ11, RS45, RS232(SNMP,USB Optional) .
3: UPS with 1 phase 220Vac/230Vac 240Vac or 110Vac/120Vac input and output
4: UPS with high efficnecy up to 93%, and input power factor correction 0.99
Key Features
• True double-conversion on line UPS
• DSP technology guarantees high performance
• Output power factor 0.8
• Maintenance bypass available
• Standard backup UPS and long backup UPS in one integrated unit
• Adjustable battery number from 16 pcs to 20 pcs
• Adjustable charging current via LCD or software (0.5A~6A)
• Wide input voltage range (110-300 VAC)
• Active input power factor correction 0.99
• 50Hz/60Hz frequency converter mode
• 3-stage extendable charging design for optimized battery performance
• SNMP/USB/RS-232 communications
UPS Application
Home, Office, Servers, Data-center, critical network devices, Sensitive electronic equipment, Telecom, Bank system, ATM, Computers, Railway, Weak electricity system integration, security system, CCTV, Army, Programmable Logic Controller (PLC), Direct Digital Controller, Building Automation System (BAS) etc.
Technical Specification
Technical Specification | |||
GREEN STAR 6K/10K ONLINE UPS SPECIFICATION | |||
MODEL | G6K (L) | G10K (L) | |
PHASE | 1 phase in / 1 phase out | ||
CAPACITY | 6000 VA / 4800 W | 10000 VA / 8000 W | |
INPUT | |||
Nominal Voltage | 208/220/230/240VAC | ||
Voltage Range | Low Line Loss | 110 VAC ± 3% at 50% Load 176 VAC ± 3% at 100% Load |
|
Low Line Comeback | 120 VAC ± 3% at 50% Load 186 VAC ± 3% at 100% Load |
||
High Line Loss | 300 VAC ± 3% | ||
High Line Comeback | 290 VAC ± 3% | ||
Frequency Range | 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz | ||
Power Factor | 0.99 @ 100% load | ||
OUTPUT | |||
Nominal Voltage | 208/220/230/240VAC | ||
AC Voltage Regulation | ± 1% | ||
Frequency Range (Synchronized Range) | 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz | ||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||
Current Crest Ratio | 3:1 (max.) | ||
Harmonic Distortion | 3 % THD (Linear Load) 6 % THD (Non-linear Load) |
||
Transfer Time | Bypass to Inverter (Line mode) | Zero | |
Inverter to Bypass (Line mode) | Zero | ||
Waveform (Batt. Mode) | Pure Sinewave | ||
EFFICIENCY | |||
Line Mode | 89% | 90% | |
Battery Mode | 88% | 89% | |
BATTERY | |||
Standard Model | Battery Type | 12 V / 7 AH | 12 V / 9 AH |
Numbers | 16 | 16 | |
Typical Recharge Time | 9 hours recover to 90% capacity | ||
Charging Current | Default:1.0 A ± 10%, Max.:2.0A ± 10% | Default:1.0 A ± 10%, Max.:2.0A ± 10% | |
Float Charging Voltage | 218.4 VDC ± 1% | ||
Long-run Model | Battery Type | Depending on applications | |
|