user login

True Online Double Conversion UPS with Pure Sine Wave and LCD Display 1Kva - 20Kva

Place of Origin: Zhejiang

Company Profile

Location: Shenzhen, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: Uninterrupted Power Supply, Offline UPS, High Frequency Online UPS

Product Detail

Model No.: Green Star Series 1-20Kva

Product Description

 

True Online Double Conversion UPS with Pure Sine Wave and LCD Display 1Kva - 20Kva

Model:High Frequency Online UPS Green Star Series 1K-20Kva (1ph in / 1ph out) (3ph in / 1ph out)

 

Quick Read

1: Online UPS 1 - 10Kva with Single Phase Input / Output, 10 - 20Kva with 3 Phase Input, Single Phase Output 

2: UPS with RS232/DB-9 Communication port

3: Output power factor 0.8  

4: DSP technology guarantees high performance    

5: N + X Parallel Function for UPS Capacity 6K - 20Kva

 

Key Features    
• True double-conversion on line UPS
• DSP technology guarantees high performance    
• Output power factor 0.8  
• Standard backup UPS and long backup UPS in one integrated unit
• Adjustable battery number from 16 pcs to 20 pcs
• Adjustable charging current via LCD or software (0.5A~6A)
• Wide input voltage range (110-300 VAC)  
• Active input power factor correction 0.99
• 50Hz/60Hz frequency converter mode

• 3-stage extendable charging design for optimized battery performance

• Maintenance bypass available

• RJ11, RJ45, SNMP/USB/RS-232 communications

 

 

Technical Specification

 

Technical Specification
GREEN STAR 6K/10K ONLINE UPS SPECIFICATION
MODEL G6K (L) G10K (L)
PHASE 1 phase in / 1 phase out
CAPACITY 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Nominal Voltage  208/220/230/240VAC
Voltage Range Low Line Loss  110 VAC ± 3% at 50% Load
176 VAC ± 3% at 100% Load 
Low Line Comeback  120 VAC ± 3% at 50% Load
186 VAC ± 3% at 100% Load 
High Line Loss  300 VAC ± 3% 
High Line Comeback  290 VAC ± 3% 
Frequency Range 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Power Factor 0.99  @ 100% load
OUTPUT
Nominal Voltage  208/220/230/240VAC
AC Voltage Regulation  ± 1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion 3 % THD (Linear Load) 
6 % THD (Non-linear Load)
Transfer Time Bypass to Inverter (Line mode) Zero
Inverter to Bypass (Line mode) Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
Line Mode 89% 90%
Battery Mode 88% 89%
BATTERY
Standard Model Battery Type 12 V / 7 AH 12 V / 9 AH
Numbers 16 16
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current  Default:1.0 A ±  10%,           Max.:2.0A ±  10% Default:1.0 A ±  10%,          Max.:2.0A ±  10%
Float Charging Voltage  218.4 VDC ±  1%
Long-run Model Battery Type Depending on applications
Numbers 16-20** (adjustable)
Charging Current  Default:
Post Buying Request